Hoshizaki HR24A User Manual

Page of 39
19
b) Service Menu Chart
Setpoint
Service Menu Min.
Max.
Unit
Factory Setting
Description
SP
See r1 See r2 °C/°F 39°F
Cabinet setpoint. 
(compressor off temperature). 
(see r0 for compressor on temperature).
Thermistor Input (Do Not Adjust)
Service Menu
Min.
Max.
Unit
Factory Setting
Description
CA1
-25
25
°C/°F
0
Cabinet thermistor temperature offset.
CA2
-25
25
°C/°F
0
Evaporator thermistor temperature 
offset.
P1
0
1
---
0
Decimal point for °C display: 0=no, 
1=yes.
P2
0
1
---
1
Temperature display scale: 0=°C, 1=°F
P3
0
2
---
0
Evaporator thermistor:
0=not connected
1=defrost/evaporator fan
2=defrost
P8
0
250
ds
5
Temperature display delay.
Operation (Do Not Adjust)
Service Menu
Min.
Max.
Unit
Factory Setting
Description
r0
0
15
°C/°F
4°F
Temperature differential above 
setpoint for the compressor to 
turn on.
r1
-99
r2
°C/°F
34°F 
Minimum cabinet setpoint.
r2
r1
99
°C/°F
52°F 
Maximum cabinet setpoint.
r3
0
1
---
0
Locked setpoint. 0=no, 1=yes
r4
0
99
°C/°F
0
Energy saving and overcooling 
Do not adjust.
r5
0
99
°C/°F
0
r6
0
240
min.
30
Compressor Protection (Do Not Adjust)
Service Menu
Min.
Max.
Unit
Factory Setting
Description
C0
0
240
min.
2
Compressor delay at startup 
and after power interruption.
C1
0
240
min.
5
Minimum time between 
compressor starts.
C2
0
240
min.
3
Minimum compressor off time.
C3
0
240
sec.
180
Minimum compressor run time.
C4
0
240
min.
10
Compressor off time with 
defective cabinet thermistor.
C5
0
240
min.
10
Compressor on time with 
defective cabinet thermistor.