Heatcraft Refrigeration Products H-IM-82B User Manual

Page of 20
5
1.
O
wner
’s
O
per
ating
Instr
uc
tions
Table 4. Control Factory Default Settings
PTT  
Models
Temperature 
Set Points
Defrost 
Start Times
Defrost Duration 
(Maximum)
Drip
Time
Fan 
Delay
Defrost Termination
Set Point
Cooler Models
    All cabinet sizes
35˚F
Every 3 hours of
compressor run time
60 min.
38˚F
Freezer Models
    Med. & Lg. cabinet
-10˚F
4 / day
40 min.
2 min.
2 min.
65˚F
Rigging
Rigging holes are provided on all models. Caution should be 
exercised when moving these units. To prevent damage to 
the unit housing during rigging, cables or chains used must 
be held apart by spacer bars. The mounting platform or base 
should be level and located so as to permit free access of 
supply air.  The unit weather hood may be removed for the 
rigging process.  The condensing unit cover (wrapper) should 
be left in place.
Access Requirements
Provide adequate space at the compressor end of the unit for 
servicing. Provide two (2) feet of space above unit for service.
Mounting
The system requires an opening in the ceiling to the 
dimensions stated on page 3. Mounting rails are located 
at both ends of the chassis. Mounting rails may be used to 
attach unit to ceiling. Through-bolts should be insulated or 
non-conductive to prevent sweating. The chassis is weather 
stripped around the air grille and will seal to the box roof. 
The trim ring (shipped loose), when provided, should be 
installed around the air diffuser when secured with the 
hardware provided. Be sure to adhere to your local standard 
construction codes.
Inspection
1.  Each shipment should be carefully checked against the 
bill of lading.
2.  The shipping receipt should not be signed until all items 
listed on the bill of lading have been accounted for.
3.  Check packaging for signs of damage.
4.  Any shortage or damages should be immediately 
reported to the delivering carrier.
5.  Damaged material becomes the delivering carrier’s 
responsibility, and should not be  returned to the 
manufacturer unless prior approval is given to do so.
6.  When unpacking the system, care should be taken to 
prevent damage.
7.  Avoid removing the shipping base until the unit has been 
moved to the final destination.
8.  Complete warranty return card for each unit and mail to 
Heatcraft Refrigeration Products.
General Safety Information
1.  Installation and maintenance to be performed only by 
licensed contractor.
2.  Ensure that the structural integrity of the box can 
withstand the weight of the 
 (See page 2, Table 3 for 
unit weights).
3.  Avoid contact with sharp edges and coil surfaces.  
They are a potential injury hazard.  Wear gloves during 
moving and rigging.
4.  Make sure all power sources are disconnected before 
any service work is done on units.
Trim Pieces (4)
Overlap as Shown
Evaporator Grill
Self Drilling Screw
Ceiling of Walk-in.
Trim Ring