Following steps and diagram indicate location of the 
connection points required to measure manifold pressure.
Manifold pressure may be measured using a U-Tube 
Manometer or Differential Pressure Gauge. Diagram shows 
connection of both measuring devices. Only ONE DEVICE IS 
REQUIRED to measure manifold pressure.
Remove plug. Install appropriate barbed fi tting and connect 
pressure side line from U-Tube Manometer or Differential 
Pressure Gauge.
OFF 
ON 
INLET
OUTLET
GAS CONTROL KNOB 
PRESSURE REGULATOR 
ADJUSTMENT (UNDER CAP SCREW) 
INLET 
PRESSURE 
TAP 
VR8205 
WIRING TERMINALS (2) 
OUTLET 
PRESSURE 
TAP
Figure 27   - Manifold Pressure Measurement Detail
Figure 28   - Gas Valve
CHECK OUT PROCEDURE AND ADJUSTMENT
Refer to  “Differential Air Pressure Switch Check” on page 
49  when reading manifold pressure.
When measurement is complete, disconnect U-Tube 
Manometer or Differential Pressure Gauge. Be sure to 
reinstall ⅛” plug, using appropriate pipe thread sealant 
approved for use with natural and liquefi ed Petroleum 
gases.
NOTICE
Regulator cover screw must be installed at all times un-
less adjusting manifold pressure. Firing rate and manifold 
pressure must only be measured with cover screw fi rmly 
installed.