6) Evacuate through the Schrader access ports on the Parker quick connect couplings and 
charge with R-404A refrigerant vapor to a pressure of 15 to 30 PSIG.
7) Connect the refrigerant lines to the appropriate male fittings on the remote condenser 
unit first and then at the icemaker. Make a proper connection as follows:
a. Remove the protective covers from the male fitting and female coupling.
b. Apply Polyol Ester (POE) refrigerant oil or Parker Super O Lube to the entire male 
fitting, including O-ring, diaphragm, and threads, before making the connection. 
See Fig. 13.
CAUTION
Do not use thread sealant on the fittings. Use POE refrigerant oil or Parker 
Super O Lube only.
c. Make sure the male fitting and female coupling are properly aligned, then start the 
connection by hand to ensure that it is not cross threaded. 
d. Tighten the connection with a wrench until it is tight. At this point, the nut has 
covered most of the threads on the male fitting. 
e. Mark a reference line on the female coupling and the remote condenser unit or 
icemaker panel. Using a backup wrench on the back of the female coupling, tighten 
the six-sided nut of the female coupling an additional 1/6 turn. See Fig. 14.
8) If the line set exceeds 66 feet, see "II.G.5 Refrigerant Charge (Line Set Exceeding
66 Feet)" for proper charging of the unit.
Fig. 13
Fig. 12
Female Coupling
5/8" OD Discharge Line
(Insulated)
Remote Condenser Unit
3/8" OD Liquid Line
(Insulated)
Icemaker
Male Fitting
Service Loop
Apply POE Oil or 
Parker Super O Lube 
to Entire Male Fitting
THREAD 
SEALANT
Threads
Diaphragm
O-Ring
Brush
Male Fitting
DO NOT USE 
THREAD SEALANT 
POLYOL 
ESTER 
(POE) OIL
PARKER
 SUPER
O LUBE
Fig. 14
Backup 
Wrench
Reference 
Line
1/6 
Turn
Wrench
Wrench
After Tight, Tighten an 
Additional 1/6 Turn
Backup 
Wrench