Pump-out cycle always occurs on the 2nd harvest after startup. Then, depending on the 
pump-out frequency control setting (S1 dip switch 5 & 6), pump-out cycle occurs every 
cycle, or every 2nd, 5th, or 10th cycle.
d) Pump-Out Frequency Control (S1 dip switch 5 & 6)
The water tank drains at the frequency set by the pump-out frequency control.
The pump-out frequency control is factory-adjusted to drain the water tank every 10 
cycles, and no adjustment is required. However, where water quality is bad and the 
icemaker needs a pump-out more often, the pump-out frequency can be adjusted as 
shown in the table below.
Dip Switch Setting
Frequency
No. 5
No. 6
OFF
OFF
every cycle
ON
OFF
every 2 cycles
OFF
ON
every 5 cycles
ON
ON
every 10 cycles
e) Harvest Pump Timer (S1 dip switch 7 & 8)
The harvest pump timer allows the water valve to close and the pump motor to circulate 
water in the tank during the fi nal part of harvest. The water valve is open during harvest 
for a maximum of 6 minutes or the length of harvest minus 0, 10, 30, or 50 seconds 
(determined by the harvest pump timer setting), whichever is shorter. When the water 
valve closes, the pump motor energizes and runs for the time determined by the harvest 
pump timer setting.
The harvest pump timer is factory-adjusted, and no adjustment is required.
Dip Switch Setting
Time
(seconds)
No. 7
No. 8
OFF
OFF
0
ON
OFF
10
OFF
ON
30
ON
ON
50
f) Freeze Timer (S1 dip switch 9 & 10)
CAUTION
Adjust to proper specifi cation, or the unit may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent 
possible freeze-up issues. Upon termination of freeze timer, machine initiates the 
harvest cycle. After 2 consecutive timer terminations, machine will shut down, possibly 
indicating a problem.