Pelco C1619M-I User Manual

Page of 24
C1619M-I (11/07)
11
RACK MOUNTING
The Endura workstation mounts into an industry-standard 19-inch (48 cm) equipment rack. The Endura workstation occupies two rack units 
(3.5 inches or 8.9 cm) of vertical rack space. The hardware necessary to mount the Endura workstation into a rack is supplied with the unit.
The rack must meet the following requirements:
Rack standard: 19-inch EIA-310-D compliant (rear column required).
Rack column depth: 20 to 30 inches (50.8 to 76.2 cm).
Column mounting hole provisions: 10-32 UNF-2B threaded holes or square window holes on front and rear columns.
Door systems (optional): Front doors must have at least 2 inches (5.1 cm) between the Endura workstation front bezel and the inside of the 
door. Rear doors may be used only on rack columns that are more than 26 inches (66.0 cm) deep.
NOTE:  Figure 3 identifies each piece of hardware for this procedure.
To install the Endura workstation in a rack:
1. If chassis mounting brackets are not attached: Attach one mounting bracket to each side of the Endura workstation. Use four 10-32 x 0.25-inch 
Phillips pan head screws for each bracket. Attach the brackets so that the tapered ends are positioned toward the rear of the Endura 
workstation. Refer to Figure 5.
2. Remove the four rubber feet from the underside of the unit if they are attached. Save the rubber feet and screws for possible future use.
3. Attach one front-mount rail to one rear-mount rail. Make sure the rails are mounted back to back, as shown in Figure 6. Use three 
8-32 x 0.375-inch Phillips truss head screws in any of the available holes. Leave the screws loose until step 8.
Figure 6.  Assembling a Support Rail
4. Repeat step 3 for the other rail set.
WARNING:  Slots and openings in the cabinet provide ventilation to prevent the unit from overheating. Do not block these openings. 
Never place the unit near or over a radiator or heat register. When placing the unit in a built-in installation, such as a rack, be sure to 
provide proper ventilation. Allow at least one rack unit (1.75 inches or 4.44 cm) of spacing between units.
(3) SCREWS, 8-32 X 0.375
PHILLIPS TRUSS HEAD