DR4300 Circular Chart Recorder Product Manual 
12/03 
4.3.13  Setpoint Ramp/Program Set Up Group 
Introduction 
All models supporting control can be configured to ramp the setpoint between the current local setpoint 
and a final local setpoint over a timer interval of from 1 minute to 255 minutes. 
If the optional Setpoint Program feature is specified at time of purchase, then in addition to this single ramp 
capability, you can also configure a ramp/soak profile containing up to twelve segments, each with its own 
time interval. 
Setpoint ramp/program group prompts 
Table 4-11 lists all the function prompts in the setpoint ramp group.  The additional prompts associated 
with the optional twelve-segment Setpoint Program are described in Appendix C.    
For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface. Press 
FUNC  to select channel. 
Press SETUP  key until “SPRAMP” appears in the lower display. 
Press FUNC  key to select the parameters. 
Table 4-11  Setpoint Ramp Parameter Definitions 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
SP RAMP
 
 
 
 
 
ENAB 
 
DIS   [factory setting] 
SINGLE SETPOINT RAMP
 — Make selection to enable or 
disable the setpoint ramp function. Make sure you 
configure a ramp time and a final setpoint value. “SP 
PROG” must be disabled. 
ENABLE SETPOINT RAMP
 — Allows the single setpoint 
ramp prompts to be shown. 
DISABLE SETPOINT RAMP
 — Disables the setpoint 
ramp. Allows “SPPROG” option to be selected. 
TI MIN 
0 minutes to 255 minutes 
[factory setting = 0]
 
SINGLE SETPOINT RAMP TIME
 — Enter the number of 
minutes desired to reach the final setpoint or a single 
setpoint ramp. 
A ramp time of “0” implies and immediate change of 
setpoint to the final setpoint. 
FINL SP 
Within SP limits 
[factory setting = 0]
 
SETPOINT RAMP FINAL SETPOINT
 — Enter the value 
desired for the final setpoint. The controller will operate at 
the setpoint set here when ramp is ended. 
SP PROG 
 
ENAB 
DIS   [factory setting] 
SETPOINT RAMP/SOAK PROGRAM
 
Available only with controllers that contain this option. 
For reasons of convenience, the information for the 
prompts when SPPROG is enabled are included in 
Appendix C. 
ATTENTION
 “SP RAMP” must be disabled for 
SPPROG to be available.