Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
111 
4.3.17  Communication Set Up Group 
Introductions 
If the hardware supports the Modbus communication option, use the prompts in the communication set up 
group to configure communication parameters.    
Communication group prompts 
Table 4-15 lists the function prompt in the communication set up group. 
For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface. Press 
FUNC  to select channel. 
 
Press SETUP  key until “COMM” appears in the lower display. 
Press FUNC  key to select the parameter. 
 
ATTENTION 
Each pen channel must have its own unique address.  However, set the same baud rate and 
transmitter delay for both pens. 
 
Table 4-15  Communication Parameter Definitions 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
COMM 
 
DIS [factory setting] 
ENAB 
COMMUNICATION ENABLE
—Enable/disable 
communication. 
ADDRES 
1 to 99 
[factory setting = 0]
 
ADDRESS
—Specify the pen channel’s address on the 
network. 
BAUD
 
300 
600 
1200 
2400 
4800 
9600  [factory setting] 
192K 
BAUD RATE
—Specify the baud rate used by all devices 
on the network. 
XmtDLY 
NONE  [factory setting] 
10ms 
20ms 
30ms 
40ms 
50ms 
TRANSMITTER DELAY
—Specify the minimum delay 
between the end of a received message and the start of 
the response message.  
DBLBYT 
 
 
FP B 
FP BB 
FP L 
FP LB 
DOUBLE BYTE ORDER
—Determines Floating Point 
Byte order in Modbus queries. 
Big Endian 
Big Endian – Byte Swapped 
Little Endian 
Little Endian – Byte Swapped