DR4300 Circular Chart Recorder Product Manual 
12/03 
5.2  Input Calibration Minimum and Maximum Range Values 
Minimum and maximum range values 
You should calibrate the recorder for the minimum (0 %) and maximum (100 %) range values of your 
particular sensor.  If your recorder has two (pens) inputs, calibrate each input separately. 
Make sure the correct input is on display INP1 or INP2; use the 
FUNC
 key to select the input.  
Select the voltage or resistance equivalent for 0 % and 100 % range values from Table 5-1. Use these values 
when calibrating your recorder.