Emerson 350-500VA Leaflet

Page of 2
PowerSure
 PST
Quick-Start Guide for 350-500VA; 120V
W
HAT
S
 I
N
 T
HE
 B
OX
• Quick-Start guide
• PowerSure family user manual on CD (also 
at 
• Warranty card
• RJ-11 cord, 7 ft. (2.1 m)
• USB cable, 6 ft. (1.8m)
For more details, refer to the PowerSure user 
manual on CD.
Para una información más detallada, consulte 
el manual
 
del usuario de la familia PowerSure 
en el CD.
Refer to Bottom for
Cautionary Markings
Power ON/OFF/
Alarm Silence
Utility Indicator*
(Green)
Site Wiring Fault Indicator
(Red)
Fault Indicator* (Red/Green)
USB port
Circuit
protector
Output receptacles 
(surge protection
only)
Data Line 
Protection 
Connectors
TOP OF UPS
LEFT SIDE OF UPS
RIGHT SIDE OF UPS
Power cord
6.5 ft. (2m) 
Output receptacles
(battery backup and 
surge protection)
I
NSTALLATION
Read all safety, installation and operating instructions in the PowerSure family user 
manual on the included CD or at 
 before operating the UPS. Adhere 
to all warnings on the unit and in the manual.
1. Install the UPS indoors in a controlled environment, where it cannot be accidentally 
turned off. Place it in an area of unrestricted airflow around the unit, away from 
water, flammable liquids, gases, corrosives and conductive contaminants. Maintain 
a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an 
ambient temperature range of 32°F to 104°F (0°C to 40°C).
2. Plug the PST’s power cord into an AC outlet. Check the Site Wiring Fault Indicator 
on the rear; if it is illuminated, refer to the Troubleshooting section.
3. Plug any computers and monitors into the orange receptacles for battery backup 
and surge protection; other office machines that do not exceed the capacity of the 
UPS may be plugged into either of the two (2) black receptacles, which provide 
surge protection only.
4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.
5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indicator will illuminate (green).
6. Turn on connected equipment.
Plug this type of equipment 
into black receptacles ONLY
Plug computers, monitors, 
routers and cash registers into 
orange receptacles
Inkjet 
printers
Scanners
Fax 
machines
C
ONTROLS
 
AND
 I
NDICATORS
This button controls output power to 
the connected load and has three 
functions:
•Turns the PowerSure PST ON
•Turns the PowerSure PST OFF
•Silences PowerSure PST alarms
TURN THE UPS ON: Press and release the 
main ON/OFF button to start the UPS. An 
audible alarm will sound briefly.
TURN THE UPS OFF: When the PST is ON, 
hold the main ON/OFF button down for more 
than 2 seconds to shut it down. An audible 
alarm will sound briefly.
SILENCE AN ALARM: When a UPS alarm is 
active, press and release the main ON/OFF 
button to silence the audible alarm (Excep-
tions: low battery, overload and overtempera-
ture). DO NOT hold the button down for more 
than 2 seconds or the PST will shut down.
CHECK THE PST’S CONDITION: Three sta-
tus indicators on the front of the UPS illumi-
nate to specify the status of the UPS (see 
Troubleshooting section for details).
SITE WIRING FAULT INDICATOR (AMBER)
The Site 
Wiring 
Fault Indi-
cator on 
the top of 
thePST, 
as shown, 
illumi-
nates amber when the UPS detects a line-
neutral reversal or a poor neutral-ground. 
(See Troubleshooting Chart if indicator is 
illuminated.)
Site Wiring 
Fault
Indicator 
(Amber)
Top of UPS
S
PECIFICATIONS
Model Number
PA350-120U
PA500-120U
Model Rating VA / W
350/225
500 / 300
DIMENSIONS: in (mm)
Unit W x D x H
6.6 x 9.8 x 3.7
(168 x 250 x 95)
6.6 x 9.8 x 3.7
(168 x 250 x 95)
Shipping W x D x H
9.4 x 13.8 x 5.6
(238 x 350 x 142)
9.4 x 13.8 x 5.6
(238 x 350 x 142)
WEIGHT: lbs (kg)
Unit
11.7 (5.3)
13.5 (6.1)
Shipping
12.1 (5.5)
13.9 (6.3)
INPUT AC PARAMETERS
Surge Protection
603J
Voltage Range Without
Battery Operation
98VAC - 140VAC ±3VAC
Frequency
57 - 63 Hz (±0.4Hz)
Input Power Cord
6.5 ft.attached, w/ NEMA 5-15 P
OUTPUT AC PARAMETERS
Output Receptacles
(3) NEMA 5-15R (orange) battery 
backup+surge protection
(2) NEMA 5-15R (black) surge 
protection
Voltage (Battery Mode)
120VAC ±8%
Output Current
2.9 A
4.2 A
Waveform (Battery Mode)
Stepped Sinewave
Frequency (Battery Mode)
60Hz ±1Hz
Overload Warning 
>100%
Overload Shutdown 
>110%
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead 
acid
Quantity x Voltage x Rating 1 x 12V x 5 Ah
1 x 12V x 7 Ah
Transfer Time
4 – 6 ms typical
Back-up Time:
At 77°F (25°C), resistive loading, w/ 
fully charged batteries:
Full load
5 minutes
3 minutes
Half load
16 minutes
15 minutes
Recharge Time
12 hours to 90% capacity, after full 
discharge into resistive load
ENVIRONMENTAL
Operating 
Temperature
+32°F to + 104°F 
(0°C to +40°C)
Storage
Temperature
+5°F to + 122°F (-
15°C to +50°C)
Relative 
Humidity
0% to 95%, non-
condensing
Operating 
Elevation
Up to 10,000 ft. 
(3000 m) at 86°F 
(30°C) w/o 
derating
Audible Noise
< 40 dBA, at 1 
meter
AGENCY
Safety
UL 1778, c-UL 
Listed
Surge
ANSI C62.41, 
Category A, Level 
3, (IEEE 587, 
Category A);
EN61000-4-5, 
Level 3, Criteria A
ESD
EN61000-4-2, 
Level 3, Criteria A
Susceptibility
EN61000-4-3, 
Level 2, Criteria A
Electrical Fast 
Transient/Burst
EN61000-4-4, 
Level 3, Criteria A
Emissions
FCC Part 15, 
Subpart B,
Class B
Harmonics EN61000-3-2
Conducted 
Immunity
EN61000-4-6
Flicker EN61000-3-3
Transportation
ISTA Procedure 
1A
C
OMMUNICATIONS
The PowerSure PST has a USB interface port for communication that will work with the built-in Microsoft 
Power Manager software on the user’s PC, if the PC is so equipped. It will provide UPS status and man-
ages the automatic, orderly shutdown of the computer. The UPS (USB) communications meets HID stan-
dard, version 1.11. All USB models are compatible with Microsoft Windows 2000, Windows XP and Mac 
OS 10.2 or later. All USB models ship with a 6 ft. (1.8m) USB cable.