“ZNR” Transient/Surge Absorbors, Type E, Type CK, SC
– EC129 –
“Z
N
R
” T
ra
nsien
t/S
urge Abso
rb
ers
1.
Precautions  for Safety
The “ZNR” Transient/Surge Absorbers (hereafter referred to as “The ZNR Varistors”) may fail in a short-circuit mode 
or in an open-circuit mode, when subjected to severe  conditions  of  electrical, environmental and/or me 
chanical 
stresses beyond their specifi 
ed “Ratings” and specifi 
ed “Conditions”, resulting in burnout, fl 
aming or glowing in the 
worst case.
Following “
Precautions for Safety” and “Application Notes” shall be taken in your major consideration. If you have 
a question about the “Precautions for Handling”, please contact our engineering section or factory.
Precautions  for Handling
“ZNR” Transient/Surge Absorbers, Type E
“ZNR” Transient/Surge Absorbers, Type CK, SC
1.1 Operating Conditions
1.1.1 The ZNR Varistors shall not be operated beyond 
t h e   s p e c i f i e d   “ R a t i n g s”   a n d   “ E nv i ro n m e n t a l  
Conditions” in the Catalog or the Specifi 
cations to 
prevent them from deterioration, breakdown, fl 
aming 
or glowing.
●  The ZNR Varistors shall not be operated exceeding 
the specifi 
ed “Maximum Allowable Voltage” in the 
Catalog or the Specifi cation.
●  The ZNR Varistors shall not be subjected to 
energy levels above their specifi 
ed “Maximum 
Energy Ratings” in the Catalog or the Specifi cations.
●  In case of application to repeated surge/
overvoltages, the ZNR Varistors shall not be
subjected to surge currents and energy levels 
above the specifi 
ed maximum ratings in “Impulse 
Life Rating” in the Catalog or the Specifi cations.
●  When surge/overvoltages are intermittently
applied to the ZNR Varistors with short durations, 
the devices shall not be operated beyond the 
specifi ed “Rated Power” in the Catalog or the 
Specifi cations.
●  The ZNR Varistors shall not be operated beyond 
the specifi 
ed “Operating Temperature Range” in 
the Catalog or the Specifi cations.
●  It is recommended that the ZNR Varistors, if 
not fused, shall be located away from other 
combustible components.
1.1.2 The ZNR Varistor shall be operated correctly
under following conditions to prevent Varistors from 
causing mechanical damages and ruptures and to 
protect human from serious injuries;
●  The ZNR Varistors shall not be operated
exceeding the specifi 
ed “Maximum Allowable 
Voltage Ratings” in the Catalog.
●  The ZNR Varistors shall not be operated beyond 
the “Maximum Peak Current Ratings” in the 
Catalog.
●  S o me  safet y  countermeasure such as a
p r o t e c t i v e   c a s e   c o v e r i n g   t h e   Va r i s t o r   i s
recommended, if necessary.
1.1.3  When the ZNR Varistors are applied to between 
a live part and a metallic chassis of equipment, 
following safety countermeasures shall be taken to 
protect human from electric shock.
A) The  metallic  chassis shall be earthed to the 
ground.
B) The live part shall be equipped with a protective 
cover for preventing electric shock.
2. Application Notes
2.1 Protective Devices for Varistors
2.1.1 The ZNR Varistors shall be protected from serious 
accidents due to unexpected physical phenomenor 
by following safety countermeasures.
●  In case of “Across-the Line Use”, the ZNR
Varistors shall be protected by connecting a 
ground fault circuit interrupter of fusing in series 
to the devices. (See Table 1)
●  In case of “Line to Ground Use”, the short-circuit 
of the Varistor may not blow the current type 
fuse due to the grounding resistance (between 
Line and Ground), which may cause fl 
aming or 
burnout of the devices in the worst case.
Following safety countermeasures (A or B) are
recommended;
A) Connecting a “leakage current circuit breaker” in 
series to the Varistor to be protected. (See Table 
1)
B) Use current type fuses and a thermal type fuse 
which are thermally coupled each others. (See 
Table 1)
✽ Fuses shall use rated voltages appropriate for circuits.
✽ Finally, confi rm that the secondary disaster does not 
occur even if the ZNR mounted on equipment breaks.
✽ Set a thermal fuse to get high thermal conductivity 
with ZNR.
Series
ERZC20EK
첸첸첸 ERZC32첸K첸첸첸
ERZVS34C
첸첸첸
ERZC40CK
첸첸첸
Current Fuse
(Line  - Line)
10 A max.
20 A max.
20 A max.
Thermal. Fuse
(Line  - Ground)
100 to 120 °C 5 A 100 to 120 °C 10 A 100  to  120 °C 10 A
●  Recommendation fuse
Apr. 2008