Radia Eclipse Dimmer Modules
3
RE-DM4 and RE-DM6 RADIA Eclipse Dimmer Modules
Caution: Pre-Installation Notes

All Class 1 and 2 wiring must be connected to their dedicated terminals.

Class 1 wiring should be connected through the top of the enclosure, and Class 2 wiring through the 
bottom.

Load conductors must be same size as line conductors, regardless of connected load.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times, and maintain 12” (30.48 cm) clearance around the 
top and bottom.

Test loads for shorts before connecting.

Class 2 wiring must be rated 300V or higher.

For indoor use only.

AC lighting loads only.

This module may require extra power from the AxLink connection or an external power supply 
connected to the control card.
RE-DM4 4-pin module connector (male)
The 4-pin male module connector for the RE-DM4 is illustrated in FIG. 2.
Line-In Connections

Using two feeds for Line 1 and Line 2 provides two 2400 W inputs.

With a jumper, Line 1 and Line 2 provides a single 2400 W input.
T
his unit should be installed only by qualified electrical personnel, and in compliance 
with all national electrical codes, local codes and ordinances.
To prevent possible personal injury or death, disconnect power to the enclosure at 
the breaker box
 before attempting to work with any AMX Lighting modules.
FIG. 2  
4-pin Male Module Connector for the RE-DM4
FIG. 3  
Line-In Connections for the RE-DM4
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
 
Single 2400 W  Input with jumper
Dual 2400 W Inputs without jumper