AMX RE-DM4 User Manual

Page of 90
Installation
12
 RE-DM4 and RE-DM6 RADIA Eclipse Dimmer Modules
Conduit
Conduit runs depend on the enclosures you use and their AMX Lighting modules. All enclosures have conduit 
knockouts on the top for high-voltage connections, and knockouts on the bottom for low-voltage connections.
All conduit knockouts allow for 1/2, 3/4, and 1-inch (12.7 mm, 19.0 mm, and 25.4 mm) conduits as shown in 
FIG. 11. 
You should also consider these recommendations prior to installing enclosures:

Install separate conduit for lighting loads. The recommended knockout for loads is located on the 
top center of the enclosure. 

Install separate conduit for the 120 VAC wiring to the line input terminal block. The recommended 
knockouts for incoming power feeds are located on the top-left and top-right sides of the AMX 
Lighting enclosure. 

Install separate conduit for low-voltage signals for dry closures and AxLink connections. The 
recommended knockout for these control connections is located on the bottom of the enclosure. 

Additional knockouts are on the bottom-left and bottom-right sides of the enclosures for alternate 
low-voltage connections.
FIG. 11  
Knockout locations (RDA-ENC2 used as example)
TOP
BOTTOM
LEFT SIDE
FRONT
RIGHT SIDE
B
A
C
A
C
A
E
G
F
A
E
D
D
Knockout
Knockout
Knockout
Knockout
Knockout
Knockout
All knockouts
are for 1/2" (1.26 cm),
3/4" (1.90 cm), and
1" (2.54 cm)
conduit
A = 3.94" (100.0 mm)
B = 6.03" (153.1 mm)
C = 3.00" (76.2 mm)
D = 1.00" (25.4 mm)
E = 9.75" (24.76 cm)
F = 6.00" (15.24 cm)
G = 11.90" (30.22 cm)
Install the control modules according to local and National Electrical Code (NEC) regulations.