Generac Power Systems R-200A User Manual

Page of 16
 4 
General Information
R-panel Technical Manual
 
Switch Position
Condition System 
Low 
Low 
Low 
High 
Over 
Over 
Manual 
Auto 
Off
 Ready 
Fuel 
Bat 
Oil 
Temp 
Speed 
Crank
Generator Switch is 
OFF 
OFF 
OFF 
OFF 
OFF 
 
 
O
in the OFF Mode
System Ready for 
ON 
OFF 
OFF 
OFF 
OFF 
 
O
Automatic Start
Generator Switch is 
OFF 
OFF 
OFF 
OFF 
OFF 
O
in the MANUAL Mode
Weekly Exerciser 
Flashing  Flashing  Flashing 
Flashing 
Flashing 
O
is not Set (Note A) 
 
           
(---------------------------------------1 sec rate -------------------------------------)
Battery Voltage <12.2V 
ON 
 
 
 
 
O
for > 1 minute 
 
 
(Non-Latching)
Battery Voltage <6V 
OFF 
ON 
 
 
 
 
O
For > 0.05 seconds
Unit Shutdown due 
OFF 
ON 
 
 
 
O
To Low Oil Pressure
Unit Shutdown due 
OFF 
 
ON 
 
 
O
To High Cooant Temp
Unit Shutdown due 
OFF 
 
 
ON 
 
O
To Engine Overspeed
Unit Failed to Start 
OFF 
 
 
 
ON 
O
During it's Crank Cycle
Utility Voltage is 
Flashing 
 
 
 
 
O
< 60% of Nominal 
1 sec rate
Unit Shutdown due 
OFF 
 
Flashing 
 
 
O
To Low Coolant Level
Engine Speed Signal 
OFF 
 
 
Flashing 
 
O
Fault/RPM Signal Loss
Control Board is  
Flashing 
 
 
 
 
O
In GTS Mode 
5 sec ON, 1 sec OFF
DIP Switch #5 is 
OFF 
ON 
ON 
ON 
ON 
ON 
O
not set correctly
@ = Low Fuel Pressure is a Yellow LED and will be ON when fuel pressure is less than 5 inches Water Column
X = indicates that the LED can be ON or OFF depending on the Operating Mode (i.e. Manual, OFF or Auto)
Note A: a RED LED fault indication has priority over the flashing LED's used to indicate exercise time not set