Raritan Engineering KX2-832 User Manual

Page of 321
 
Chapter 7: Device Management 
 
 
143
 
Manage KVM Target Servers Associated with Outlets (Port Page) 
This Port page opens when you select a port from the Port Configuration 
page that is connected to a target server. From this page, you can make 
power associations, change the port name to something more 
descriptive, and update target server settings if you are using the 
D2CIM-VUSB CIM. The (CIM) Type and the (Port) Name fields are 
prepopulated; note that the CIM type cannot be changed. 
A server can have up to four power plugs and you can associate a 
different power strip with each. From this page, you can define those 
associations so that you can power on, power off, and power cycle the 
server from the Port Access page. 
To use this feature, you will need: 
• 
Raritan remote power strip(s) 
• 
Power CIMs (D2CIM-PWR) 
 
To make power associations (associate power strip outlets to 
KVM target servers): 
Note: When a power strip is associated to a target server (port), the 
outlet name is replaced by the target server name (even if you assigned 
another name to the outlet). 
1.  Choose the power strip from the Power Strip Name drop-down list. 
2.  For that power strip, choose the outlet from the Outlet Name 
drop-down list. 
3.  Repeat steps 1 and 2 for all desired power associations. 
4.  Click OK. A confirmation message is displayed. 
 
To change the port name: 
1.  Type something descriptive in the Name field. For example, the 
name of the target server would be a likely candidate. The name can 
be up to 32 alphanumeric characters and can include special 
characters. 
2. Click 
OK.