Siemens X-100 User Manual

Page of 121
Product Characteristics 
 
4.1 SCALANCE X108 
Power indicator (green LED) 
The status of the power supply is indicated by two green LEDs: 
 
Status 
Meaning 
lit green 
Power supply L1 or L2 is connected. 
not lit 
Power supply L+ is not connected or <14 V 
Port status indicator (green/yellow LEDs) 
The status of the ports is indicated by eight LEDs: 
 
Status 
Meaning 
Port 1 through 8 LED lit green  
TP link exists, no data reception 
Port 1 through 8 LED lit yellow 
TP link exists, data received at TP port 
Ports 1 through 8 LED flash yellow  Setting or display of the fault mask 
 
4.1.8 
SCALANCE X108 Technical Specifications 
Technical Specifications of the SCALANCE X108 
 
Ports 
Attachment of DTEs or network components over 
twisted pair 
8 x RJ-45 sockets with MDI-X pinning 10/100 
Mbps (half/ full duplex) 
Connector for power supply 
1 x 4-pin plug-in terminal block 
Connector for signaling contact 
1 x 2-pin plug-in terminal block 
Electrical Data 
Power supply 
2 x 24 V DC 
(18 - 32 V DC) 
safety extra-low voltage (SELV) 
Power loss at DC 24 V 
3.36 W 
Current consumption at rated voltage 
140 mA 
Overvoltage protection at input 
PTC resetable fuse (0.6 A / 60 V) 
Permitted Cable Lengths 
Network span parameter/TP cable length 
0 – 100 m 
 
 
 
0 – 85 m 
 
IE FC standard cable with IE FC RJ-45 plug 180 
or  
over IE FC outlet RJ-45 with 0 - 90 m IE FC 
standard cable + 10 m TP cord  
IE FC marine/trailing cable with IE FC RJ-45 plug 
180  
or 
0 - 75 m IE FC marine/trailing cable + 10 m TP 
 
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line 
4-6
 
Commissioning Manual, 1,