Ethernet Communication Module DVPEN01-SL
 
DVP-PLC Operation Manual 
20 
5.2 Basic 
Settings 
The basic settings include parameters as module name, language, enabling Modbus TCP and time 
correction.
 
„
 
Setting up DVPEN01-SL basics 
 
 
 1. 
Module 
Name: 
There can be many DVPEN01-SL modules in the network. Thus, you can set up a module name 
for each module to identify the module when you need to use them. 
2. Module Language: 
You can select a language for each module name, and the windows will be displayed in the 
selected language. 
3. Enable Modbus TCP: 
To enable or disable Modbus TCP. When Modbus TCP is disabled, WPLSoft will not be able to 
upload or download. 
4. Enable time correction: 
DVPEN01-SL adopts NTP (Network Time protocol), which means it can acquire correct time 
automatically from the time server in the network and correct the RTC in the MPU every fixed 
period of time to ensure correct time in the MPU. The default setting of this function is “disable”. 
5. Start Daylight Saving Time: 
Daylight Saving Time; also known as summer time is a conventional local time adopted by many 
countries in the world on a seasonal basis. Most commonly DST is obtained by adjusting the 
official local time forward, by one hour, for the spring, summer, and early autumn periods. 
Daylight Saving Time is not implemented in Taiwan; therefore, you do not need to check this 
item. 
6. Time Server: 
IP address of the time server. You can acquire correct time from the time server to correct the 
time in the MPU.