Jasco 15306 Leaflet

Page of 1
We recommend that installation be made by a licensed electrician.
Disconnect power at main panel prior to installing or servicing this 
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG #8-14 ) suitable for 75
º
(167
º
F).
Replace insulator before turning on electricity to unit.
INSTALLATION AND OPERATING INSTRUCTIONS TO SET ON AND 
OFF TIMES:  
Light trippers turn ON. 
Dark trippers turn OFF. Place tripper on 
dial edge as shown in figure and set 
point of each tripper to desired oper-
ating time. Note if selected time is AM 
or PM. Hold tripper against dial edge 
and firmly tighten knurled screw.
120VAC/60Hz
O
F
F
O
N
TIM
E
ON TIME 
(Light Tripper)
MANUAL 
ON 
LEVER
MANUAL 
OFF 
LEVER
OFF TIME 
(Dark Tripper)
Knurled Screw
Dial Calibrations
HEAVY DUTY  
MECHANICAL 
TIME SWITCH
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET DIAL TO TIME:
Turn dial counter-clockwise until correct time is indicated by 
arrow on nameplate.
FOR TEMPORARY MANUAL OVERRIDE:
Press down lever on right of nameplate to turn ON. Press down 
lever on left of nameplate to turn OFF. CAUTION: Do not rotate 
dial for manual override.
TO REMOVE MECHANISM FROM CASE:
Press lever near case latch to release mainplate and swing the 
movement out. To replace, insert mainplate projections in slots 
opposite latch and swing movement in until it latches.
15306
 
24 HOUR TIME SWITCH
SWITCH: 
SPST
CONTACT RATINGS: 
40 AMP 120-277VAC 
1000VA (120-277) PILOT DUTY
 
40 AMP TUNGSTEN 120VAC  120-277VAC SINGLE PHASE
 
20 AMP INDUCTIVE 
2HP 120VAC; 5HP 240VAC
TIMING MOTOR: 
120VAC 60Hz
POWER CONSUMPTION:  3 WATTS MAX
For seperate motor terminals, remove 
bridge from terminals L & 1
2
X
L
H
N
M
1
FOR 120 VAC
GE5360-41K2
469D
LOAD
Removable 
Bridge
15306 
MANUAL VERSION 1
12/15/09
WWW.JASCOPRODUCTS.COM