Toshiba Black Gold Series Leaflet

Page of 2
BUILT FOR EXTREME ENVIRONMENTS
*UPSblkgldfly051205*
UPS    ADJUSTABLE SPEED DRIVES    MOTORS    CONTROLS   INSTRUMENTATION     PLC
 
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041
Tel (713)466-0277   Fax (713)892-5212
US (800)231-1412   Canada (800)872-2192   Mexico 01(800)527-1204
www.toshiba.com/ind
Copyright 8/2006
Available Through:
Toshiba’s  Black  Gold  UPS  is  built  for  harsh  industrial  environments  subjected  to  shock  and  vibration.  
The  Black  Gold  Series  features  a  robust  steel  enclosure  (3U),  an  intelligent  LED  status  display,  an  input 
isolation  transformer,  hot-swappable  slide-out  battery  modules,  front  output  receptacle  breakers,  RS-232C 
and  remote  contacts.  This  system  combines  true  on-line  technology,  state-of-the-art  electronics  and  the  
Toshiba name to offer one of the most reliable UPS on the market.
Black Gold Series Specifications
General 
Information
Model Number
   UC1A1A020C6RKBIG
UC1E1E020C5RKBIG
Rated Output Capacity
 2000 VA (1400 W)
External Dimensions (W x D x H)
16.75 in x 24.0 in x 5.25 in (425 mm x 610 mm x 133 mm)
Input
Rated Voltage
120 VAC, Single Phase
230 VAC, Single Phase
Voltage Variation
+10% to -30%
Rated Frequency
50/60 Hz
Power Factor
Greater than .98 when in inverter mode
Harmonic Currents
Less than 5% THD
Battery
DC Nominal (Voltage Range)
72 VDC (57.6 – 82.8 VDC)
Float Charge (Regulation)
82.8 VDC (±2%)
Ripple Voltage
0.5 % R.M.S.
Rated Back-up Time when fully charged at 
77
o
F (25
o
C)
6 min at full load
18 min at half load
Recharge Time
Maximum 24 hrs to 100% (90% recharge after 8 hrs)
Rated Charge Time
0.40 Amps
Type of Batteries
Sealed lead-acid
Output
Rated Voltage (Single Phase)
120 VAC
230 VAC
Output Voltage Regulation
±3%, steady state
Output Frequency
50/60 Hz ±0.5% in free running mode  
(Line sync range ±1 Hz)
Output Voltage Waveform
Computer-grade sinewave with less than 3.0% THD
Rated Current (RMS)
16.6 Amps
8.6 Amps
Rated Power Factor
.7 lagging
Maximum Overload Capacity
150% for 60 sec
Voltage Transient Characteristic
± 5% under 100% load step change
Crest Factor
3.0
Environment
Operating Temperature
32 to 104
o
F (0 to 40
o
C), optimal at 77
o
F (25
o
C)
Storage Temperature
-4 to 104
o
F (-20 to 40
o
C)
Operating Humidity
30% to 90% (no condensation)
Altitude
Less than 3000 ft (1000 m) above sea level
Net Weight
119 lbs (54 kg)
111 lbs (50 kg)
Acoustical Noise
<45 dB at maximum output, measured 3.3 ft (1 m) from front panel
Efficiency (AC-DC-AC)
82%
Bypass
An automatic transfer of load to bypass switch (< 4mS-transfer time) may be caused by an overload of the inverter output, or by an 
internal fault condition. Also, the load can be manually transferred to bypass by putting the rocker switch in the STOP position.
Interface
Dry Contact
Bypass, battery low, and on-line signals
DB9 male connector
RS232 ASCII
Pins 1 through 8
DB9 female connector
Receptacle
3 5-15R (Duplex)
3 IEC320 (Duplex)
Options
RemotEye I
I
®
SNMP and web-based monitoring