Powerware 5140 User Manual

Page of 4
Technical Specifications
1
The lead-acid batteries typically used in a
UPS are considered viable as long as they
can maintain backup times of at least half
that of new batteries. The illustration to the
right shows that batteries that are constantly
trickle charged (as are virtually all other UPS
batteries on the market today) reach the end
of their useful life in less than half the time
of batteries charged using ABM. ABM uses a
patented three-stage charging technique that
not only doubles battery service life, but
also optimizes battery recharge time and
provides up to a 60-day advanced notifi-
cation of pending end of useful battery life.
Advanced Battery Management (ABM™) Technology Doubles Battery Service Life
Data based upon tests performed by an independent battery manufacturer.
E
L E C T R I C A L
I
N P U T
Voltage
200, 208, 220, 230, & 240 Vac user-selectable; 
see Model Selection Guide for default settings
Normal Voltage 
±20% of nominal voltage without using batteries
Range
Extended Voltage
160-288V without using batteries (set via front panel)
Range
Frequency
50/60 Hz, ±3 Hz (+5/-3 Hz with extended voltage range)
Connection
Hardwired
Efficiency
96%
E
L E C T R I C A L
O
U T P U T
Power Out
6000 VA/6000 Watts
Voltage Range 
±10% of nominal voltage
(online)
Voltage Range 
±5% of nominal voltage
(on battery)
Wave Form
Sine Wave
(on battery)
Frequency
Same as input (±0.5% during battery operation)
Connections
Receptacles or hardwired; see Model Selection Guide
Max Current
29A at 208 Vac; 26A at 230 Vac
Output Protection
Resettable circuit breakers
B
AT T E R Y
Type
Maintenance-free, sealed, valve-regulated lead-acid 
(VRLA), (28), 12V 5 AH
Extended Batteries
Maximum of 2 Extended Battery Modules (EBMs)
Backup Time
See Battery Run Times table 
Recharge Time
<3 hours to 80% usable capacity
Extended Battery 
<10 hours to 80% usable capacity
Recharge Time
C
O M M U N I C AT I O N S
Serial Ports
(2) Serial communication ports for use with power 
management software and installable option cards, 
including ConnectUPS SLC-EM SNMP Adapter and the 
Port Expander Card
User LEDs
Normal Operation (green), On Battery (yellow), 
On Bypass (yellow), and Alarm (red)
LCD
Two-line LCD with three button control
LCD Languages
Danish, Dutch, English, French, German, Spanish,
Italian, and Japanese
Front Panel Buttons
On, Off, and Alarm Silence/Self Test
Communications 
6-foot communication cable included
Cable
E
N V I R O N M E N TA L
A
N D
S
A F E T Y
Operating 
10°C to 40°C (25°C for optimal performance)
Temperature
Transit Temperature -20°C to 55°C
Storage Temperature 0°C to 25°C
Humidity (Operation) 20 to 80% (noncondensing)
Humidity 
5 to 95%
(Non-operating)
Operating Altitude
0 to 10,000 feet (non-operating: 0 to 30,000 feet)
Audible Noise
55 dBA at 1 meter
Safety Markings
UL, CSA, NOM. Models PW5140 6000i and 
PW5140 6000 HW also CE and VDE
Safety 
UL1778; CSA22.2 No.107.1,No.107.2,No.950; CB 
Certifications
Bulletin No.86AI; EN50091-1; EN60950; 
EMKO-TSE207/95; NOM-019-SCFI-1993
EMC Markings
FCC-A; CISPR-A; VCCI
Immunity
IEC 801-2, IEC 801-3, IEC 801-4, IEC 801-5
Surge Suppression
Conforms to IEEE 587B and ANSI C62.41
REPO Port
Meets NEC code 645-11 intent and UL requirements