DANGER
Cabling instructions for vertical-mount PDUs
If your Rack PDU came with more than one line cord, select either the high-voltage 
cord or the low-voltage cord for your installation.  Use the following procedure to 
connect and route cables for Rack PDUs that you mounted vertically in the side of 
your rack cabinet:
1.
Connect the line cord that comes with this option to the inlet on the Rack PDU; 
then, remove the screw on the cable clamp 
c1d and route the line cord through the 
clamp.
Figure 65. Connecting and routing the line cord
Overloading a branch circuit is potentially a fire hazard and a shock hazard 
under certain conditions.  To avoid these hazards, ensure that your system 
electrical requirements do not exceed branch circuit protection requirements.  
Refer to the information that is provided with your IBM device for electrical 
specifiacations.  Also adhere to the following statements:
1.
If you are connecting to a 120-127 V ac power source, connect each power 
cord to a separate branch circuit.
2.
If you are connecting to a 200-240 V ac power source and the branch 
circuit rating is:
a.
13 amps or less, connect each power cord to a separate branch circuit.
b. 14 amps to 19 amps, do not connect more than two power cords to the 
same branch circuit.
c.
20 amps or greater, you may connect up to three power cords to the 
same branch circuit.