Delta Electronics DVPCP02-H2 Leaflet

Page of 2
 
 
 
Warning 
 
Please read this instruction sheet carefully before use and follow this instruction to operate the device in order to 
prevent damages on the device or injuries to staff. 
 
Switch off the power before wiring. 
 
This instruction sheet only provides introductory information on electrical specification, functions, wiring, 
trouble-shooting and peripherals for DVPCP02-H2. Details of CANopen protocol are not included in this sheet. For 
more information on CANopen protocol, please refer to relevant reference or literatures. 
 
DVPCP02-H2 is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from opearting the device 
(e.g. key or specific tools are required to open thte enclosure) in case danger and damage on the device may occur. 
 
DVPCP02-H2 is to be used for controlling the operating machine and equipment. In order not to damage it, only 
qualified professional staff familiar with the structure and operation of it can install, operate, wire and maintain it. 
 
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power, and DO NOT touch any terminal when the power is switched on. Make 
sure the ground terminal 
  is correctly grounded in order to prevent electromagnetic interference. 
 Introduction 
Thank  you for choosing Delta DVPCP02-H2 CANopen communication module. DVPCP02-H2 can be applied 
to the connection with DVP-EH2 series PLC MPU on CANopen network. 
 Features 
1. Complies with CANopen standard  protocol 
DS301v4.02 
2. Supports NMT service 
3. Supports SDO service and 1 SDO server 
4. Supports  standard Run/Error indication 
5. Supports PDO service:  Max. 8 TXPDO and 8 RXPDO, 
and supports all PDO transmission  types 
6. Able to detect low voltage 
 Product Profile & Outline 
POWER
ERR
RUN
DR 2
DR 1
IN 0
DR 0
X
16
X
16
2
3
5
4
6
7
8
9
1
G N D
S HL D
CA N -
CA N +
4 0   [1 . 5 7 5 ]
7
  
[0
.2
7
6
]
9
0
  
[3
.5
4
3
]
8 2   [3 . 2 2 8 ]
 
Unit: mm/[inch] 
 
1
 
Extension  port 
4
 
POWER indicator 
7
 
CANopen connector 
2
 
Address switch 
5
 
RUN  indicator 
8
 
DIN rail 
3
 
Function switch 
6
 
ERR indicator 
9
 
DIN rail clip 
ENGLISH 
 Specifications    
CANopen Connector 
Type 
Removable  connector (5.08mm) 
Transmission  method 
CAN 
Transmission  cable 
2 communication cables,  1 grounding cable, 1  shielded cable 
Electrical  isolation 
500V DC 
Communication 
Message  type 
PDO, SDO, SYNC (synchronous  object), Emergency (emergency  object), NMT 
Series  transmission 
speed 
10k, 20k, 50k, 125k, 250k, 500k, 800k, 1M bps (bits  per  second) 
Product  code 
83 
Equipment type 
Company ID 
477 (Delta Electronics, Inc.) 
Electrical Specifications 
Weight (approx.  g) 
130 (g) 
Current 
28mA (typical); impulse  current 125mA (24V DC) 
Voltage 
Supplied by DVP-EH2 MPU 
Environment 
Standards 
IEC 61131-2, UL508 
Noise immunity 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 1.4GHz ~ 2GHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
Storage/operation 
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution  degree 2 
Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity) 
Shock/vibration 
immunity 
International  standards: IEC61131-2, IEC 68-2-6 / IEC61131-2 & IEC 68-2-27 
Certificates 
CE, UL 
    Components 
 CANopen Connector 
To connect to CANopen network, use the connector enclosed with DVPCP02-H2 or any connectors you can 
buy in the store for wiring. 
PIN 
Signal 
Description 
GND 
GND 
CAN_L 
Signal- 
SHIELD 
Shielded  cable 
CAN_H 
Signal+ 
Reserved 
4
G ND
SH LD
C AN-
C AN+
5
3
2
1
 
 Address Switch 
The two rotary address setup switches set up the node addresses on CANopen 
network  in hexadecimal form.   
Rotary switch 
x 16
1
 
x 16
0
 
Multiple 
× 16 
× 1 
 
N
O
D
E
A
D
D
R
E
S
S
x1 6
0
x1 6
1
 
Example: If you need to set the node address of DVPCP02-H2 as 26 (1A Hex), simply switch the 
corresponding  rotary switch  of x16
1
 to “1" and the corresponding rotary switch of x16
0
 to”A”. 
Switch setting 
Description 
0x01
 
~
 
0x7F 
Valid CANopen node  address 
0, 0x80
 
~ 0xFF 
Invalid CANopen node  address 
Note: 
The changed values on switches are only 
valid when DVPCP02-H2 is re-powered. When 
DVPCP02-H2 is operating, changing the set 
value of the address will be regarded invalid.
 
 Function Switch (DIP) 
DR2 
DR1 
DR0 
Baud  rate 
OFF 
OFF 
OFF 
10kbps 
OFF 
OFF 
ON 
20kbps 
OFF 
ON 
OFF 
50kbps 
OFF 
ON 
ON 
125kbps 
ON 
OFF 
OFF 
250kbps 
ON 
OFF 
ON 
500kbps 
ON 
ON 
OFF 
800kbps 
ON 
ON 
ON 
1Mbps 
IN0 is  reserved. 
DR 2
DR 1
IN  0
DR 0
 
Note: Set up the function switch when the power of DVPCP02-H2 is switched off. Re-power DVPCP02-H2 after the 
setup is completed. 
 Extension Port 
The extension port on DVPCP02-H2 is used for the connection to the next DVPCP02-H2 or extension  modules 
of DVP-EH2  series PLC MPU. 
 Basic Operation 
 Connecting DVPCP02-H2 to DVP-EH2 Series PLC MPU 
G ND
SHLD
CAN -
CAN+
STO P
R UN
0
1
 
IN
OUT
PO WER
RUN
ERROR
BAT. LOW
DVP-20EH
DR 2
DR 1
IN 0
DR 0
 
Switch off DVP-EH2. Open the connection port on 
the right hand side of DVP-EH2 and  connect 
DVPCP02-H2 to DVP-EH2. Switch on DVP-EH2, 
and DVP-EH2 will supply power to DVPCP02-H2. 
There is no need to connect DVPCP02-H2 to an 
external  power  supply. 
 Installing DVP-EH2 and DVPCP02-H2 on DIN Rail 
STO P
R UN
0
1
 
IN
OU T
PO W ER
RU N
ER RO R
BAT. LOW
D V P - 2 0 E H
DR  2
DR  1
IN  0
DR  0
G ND
SHL D
CAN -
CAN +
 
1.  Use 35mm DIN rail. 
2.  Open the DIN rail clips on DVP-EH2 and 
DVPCP02-H2. Insert DVP-EH2 and 
DVPCP02-H2 onto the DIN rail. 
3.  Clip up the DIN rail clips on DVP-EH2 and 
DVPCP02-H2 to fix DVP-EH2 and DVPCP02-H2 
on the DIN rail, as shown in the figure. 
 Connecting to CANopen Connector 
G ND
SHLD
C AN-
CAN+
 
 
 Installation & Wiring 
1. Install DVPCP02-H2 in an enclosure with sufficient space 
around it  to allow heat  dissipation (see the figure). 
2. DO NOT place the I/O signal wires and power supply wire 
in the same wiring circuit. 
D>5 0 mm
CP 02-H 2
D
D
D
D
EH 2 PL C
D
D
 
 Control Register 
The control registers (CR) are the registers inside DVPCP02-H2. See the table below for the definitions of all 
the CRs. DVP-EH2 series PLC MPU can read or write the CR allowed through DFROM/DTO instructions.
 
CR# 
Attribute 
Content 
High byte 
Low byte 
#0 
Read 
Model name 
DVPCP02-H2 model code = H’0240 
#1 
Read 
Firmware  version 
Displaying the current firmware version in hex, e.g. V1.00 is 
indicated as H’0100. 
#2 
Read 
Length of I/O data 
Length of output I/O data 
Length of input I/O data 
#3 ~ #102 
Read/write  Input data editing area 
DVPCP02-H2 → data storage area in CANopen master 
#103 ~ #202 
Read/write  Output data editing area  CANopen master → data storage area in DVPCP02-H2 
#203 ~ #215 
Set up by the system. DO NOT use it. 
#255 
Read/write 
MPU status 
CR#255 = K0: MPU in STOP status 
CR#255 = K1: MPU in RUN status 
 LED Indicators & Trouble-Shooting
 
There are 3 LED indicators on DVPCP02-H2. POWER indicator displays the status of working power. RUN and 
ERR indicators display the working status of DVPCP02-H2 on  CANopen network. 
 Indicator Status & Flash Rate 
Indicator status 
Flash  rate 
Steady  on 
Constantly  on 
Blinking 
ISO-phase on and off with a frequency of approximately 2,5 Hz: on for approximately 
200ms followed by off for approximately 200ms. 
Single  flash 
One  short flash  (approximately 200ms) followed by a long off phase (approximately 
1,000ms).
 
Double  flash 
A sequence  of two  short flashes (approximately  200ms), separated  by an off phase 
(approximately 200ms). The sequence is finished by a long off phase (approximately 
1,000ms). 
 POWER LED 
LED status 
Indication 
How to deal with it? 
Off 
No  power 
Check the power of DVPCP02-H2 and see if the 
connection is normal. 
Green  light  steady 
on 
Normal 
-- 
 RUN LED 
LED status 
Indication 
How to deal with it? 
Off 
No  power 
Check the power of DVPCP02-H2 and see if the 
connection is normal. 
Green light  single 
flash 
DVPCP02-H2 in STOP status 
-- 
Green light blinking 
DVPCP02-H2 in 
pre-operational status 
-- 
Green light  steady on 
DVPCP02-H2 in operational 
status 
-- 
 ERR LED 
LED status 
Indication 
How to deal with it? 
Off 
Normal 
-- 
Red light  single flash 
Bus error  exceeds the  warning 
limit. 
Check if the bus connection is correct. 
Red  light  double flash  Error  control  event 
Check and make sure the bus connection is normal. 
Red light steady on 
Bus-off 
1. Check if the network connection is normal and 
re-power it. 
2. Send it back to the factory for repair if necessary. 
 
注意事項 
 
使用前請務必仔細閱讀本使用手冊,並依照本手冊指示進行操作,以免造成產品受損或人員受傷。 
 
配線時請務必關閉電源。 
 
本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部分說明,本使用說明書僅作為
DVPCP02-H2
操作指南和入門參考,CANopen 協定的詳細內容這裏不作介紹。如果讀者想瞭解更多 CANopen
協定的內容,請參閱相關專業文章或書籍資料。 
 
本機為開放型機殼,因此使用者使用本機時,必須將其安裝於具防塵、防潮及免於電擊∕衝擊意外的外殼配線
箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開),防止非維護人員操作或意外衝擊本體,造成
危險及損壞。 
 
本產品用來控制運轉中的機械及設備。為避免損壞本產品,只有合格且熟悉本產品結構及操作的專業人員才
可進行本產品的安裝、操作、配線及維護。 
 
交流輸入電源不可連接於輸入∕輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,且請
勿在上電時觸摸任何端子。本體上的接地端子    務必正確的接地,以提高產品抗雜訊能力。 
 產品簡介 
謝謝您使用台達 DVPCP02-H2 網路通訊模組。DVPCP02-H2 定義為 CANopen 通訊模組,可用於 CANopen 網路
與 DVP-EH2 系列 PLC 主機的連接。 
 
功能特色 
1. 
符合 CANopen 標準協定 DS301v4.02。 
2. 
支援 NMT 服務。 
3. 
支援 SDO 服務,支援 1 個 SDO 伺服器功能。 
4. 
支援標準 Run /Error  指示。 
5. 
支援 PDO 服務:最大支援 8 個 TXPDO 和 RXPDO;
支援所有的 PDO 傳輸類型。 
6. 
提供本機 LV 偵測。 
 
產品外觀及各部介紹 
POWER
ERR
RUN
DR 2
DR 1
IN 0
DR 0
X
16
X
16
2
3
5
4
6
7
8
9
1
G N D
S HL D
CA N -
CA N +
4 0   [1 . 5 7 5 ]
7
  
[0
.2
7
6
]
9
0
  
[3
.5
4
3
]
8 2   [3 . 2 2 8 ]
 
尺寸單位:mm/[inch]
 
1
 
擴充模組連接埠 
4
 
POWER
指示燈 
7
 
CANopen
通訊連接器 
2
 
位址設定開關 
5
 
RUN
指示燈 
8
 
DIN
軌槽 
3
 
功能設定開關 
6
 
ERR
指示燈 
9
 
DIN
軌固定扣 
繁體中文 
 
功能規格 
CANopen
連接器 
接頭 
可插拔式連接  (5.08mm) 
傳輸方式 
CAN
 
傳輸電纜 
2
條通訊線、1 條接地線、1 條遮罩線 
電氣隔離 
500V DC
 
通訊 
資訊類型 
PDO
、SDO、SYNC(同步物件)、Emergency(緊急物件)、NMT 
串列傳輸速度 
支援 10k、20k、50k、125k、250k、500k、800k、1M bps(位∕秒) 
產品代碼 
83 
設備類型 
廠商 ID 
477
(台達電子) 
電氣規格 
重量  (約, g) 
130 (g) 
電流規格 
28mA
(典型值);衝擊電流 125mA (24V DC) 
電源電壓 
由 DVP-EH2 主機提供電源 
環境規格 
標準 
IEC 61131-2
、UL508 標準 
雜訊免疫力 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 1.4GHz ~ 2GHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
操作∕儲存環境 
操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度),污染等級  2 
儲存:-25°C ~ 70°C(溫度),5 ~ 95%(濕度) 
耐振動∕衝擊 
國際標準規範  IEC61131-2, IEC 68-2-6 / IEC61131-2 & IEC 68-2-27 
認證專案 
CE
認證、UL 認證 
    各部分元件介紹 
 CANopen
通訊連接器 
與 CANopen 網路連接時,可使用 DVPCP02-H2 隨機附帶的連接器或市售的連接器進行配線。 
引腳 
信號 
說明 
GND 
GND 
CAN_L 
Signal- 
SHIELD 
遮罩線 
CAN_H 
Signal+ 
保留 
4
G ND
SH LD
C AN-
C AN+
5
3
2
1