Warning 
  ADP485-01 is an OPEN-TYPE. Please place the module in an enclosure away from airborne dust or high 
humidity and prevent electric shock or sudden shock on ADP485-01. Also, it is equipped with protective 
method such as some special tool or key to open the enclosure, so as to avoid the hazard to users or any 
damage to the module. Do NOT touch terminals when power on. 
  When many devices are connecting in serial, their Baud rate and communication format setting should be 
the same. Also, each device must have individual Unit Address. 
  I/O terminal screw should be tightened between 1.95kg-cm (1.7 in-lbs). Use copper conductor only, 
60/75°C. 
 
Introduction 
ADP485-01 is mainly designed to connect Delta product by RS-485 interface. It is equipped with surge 
absorber and limited current protection to ensure safe connection of different devices. Also, 120Ω 
terminating resistance selection is available. This module enables Delta products to connect one 
another by RS-485 interface with much concern of safety and wide application. 
ADP485-01  offers  four  different  connectors  to  enable  the  network  connection  for  Delta’s  PLC  DVP 
series, HMI DOP series, AC Motor Drive VFD series and Servo drive ASD series. 
 Product Profile 
32
6
60
3
1
0
6
,8
9
0
6
8
7
3,4
1
2
3
4
5
 
Unit: mm 
Mounting  plate 
ON/OFF of terminating resistor (default setting: OFF) 
COM1 (DB9 female) 
DIN rail (35mm) 
COM2 (DB9 male) 
RS-485 port 
Nameplate 
RJ12 
 Optional Connecting Cable 
  ADPCAB03A: ADP485-01  ASD-A connecting cable/30cm 
  ADPCAB03B: ADP485-01  ASD-B connecting cable/30cm 
 
 
ENGLISH 
 
RS-485 Network Connection with Delta Products
 
ADP485-01 
 VFD (AC Motor Drive) 
RS-485 network
RJ12
 
ADP485-01 
 DOP (HMI) 
RS-485 network
F1
F3
F2
HMI DOP Series
COM1 COM2
one by one wiring 
DB9 male connector
DB9 male connector
 
connect to COM 1
 
 
ADP485-01 
 ASD-A (Servo Drive) 
RS-485  network
Connecting cable (ADPCAB03A)
 
ADP485-01 
 ASD-B (Servo Drive) 
RS-485 network
Connecting cable (ADPCAB03B)
 
 Environmental Specification 
Environment 
Operation 
0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollutant degree 2 
Storage 
-25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Vibration/Shock 
resistance 
International  Standard:  IEC 61131-2, IEC  68-2-6  (TEST  Fc)/IEC 61131-2  & IEC 
68-2-27 (TEST Ea) 
 COM1, COM2, and RJ12 PIN Explanation 
COM1-DB9 female 
RJ12-VFD 
1
2
3
4
5
6
7
8
9
 
 
PIN 
Definition 
PIN 
Definition 
RS485- 
+15V 
RS485+ 
GND 
RS485+ 
SG- 
RS485- 
SG+ 
5, 6, 7, 8, 9: NC 
 
5, 6: Reserved 
 
COM2-DB9 male 
RJ12-ADP485-01 
5
2
1
4
3
6
7
8
9
 
 
PIN 
Definition 
PIN 
Definition 
3, 6 
RS485- 
RS-485+ 
RS485+ 
RS-485- 
5, 9 
GND 
GND 
1, 2, 4, 7: NC 
 
1, 2, 6: NC 
 Use of Terminating Resistance 
In all RS-485 installations, the cable must be correctly terminated with two sets of resistors, one set at 
each end of the network (4,000 feet maximum total cable length). This applies even if you are only 
using  one slave node connected to one master device. The terminating resistors prevent  reflection 
problems that can interfere with data transmission. The resistance value of the terminating resistors 
should match the characteristic impedance of the cable. A typical value is 120 ohms. The terminating 
resistors must be placed at the two farthest ends of the RS-485 network, regardless of where the 
master device is. In some cases master device RS-485 ports have built in or optional terminating 
resistors. Beware of your network (whether it has one node or 32 nodes) having only two sets of 
terminating resistors. 
Termination Resistor Switch
 
 Cable Connection 
ADPCAB03A 
 
DB9 male
1394 male
1
2
3
4
5
6
7
8
9
1
5
6
3
2
4
RS485 -
RS485 +
GND
 
ADPCAB03B 
 
DB9 male
Mini DIN
1
2
3
4
5
6
7
8
9
8
1
3
6
RS485 -
RS485 +
GND
 
 
注意事項 
  本機為開放型  (Open Type)  機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電
擊或衝擊意外之外殼配線箱內。另必須具備保護措施  (如:  特殊之工具或鑰匙才可打開)  防止非維護
人員操作或意外衝擊本體,造成危險及損壞。請勿在上電時觸摸任何端子。 
  在串聯通訊各個節點所連接之裝置,其通訊速率  (Baud rate)  及通訊格式  (Format)  必須設定相同以
及每個節點必須有獨立之站號位址  (Unit address)。 
  出/入配線端子鏍絲扭力為 1.95kg-cm (1.7 in-lbs),只能使用 60°C/75°C 之銅導線。 
 
產品簡介 
本產品為一轉接器,主要用於台達機電產品  RS-485串聯通訊連接之用,本轉接器內建有突波吸收及限
流保護裝置,對於連接於ADP485-01的裝置,供了更好的保護。另外並提供終端電阻  (120Ω)  選擇開關,
不需外加。因此本產品提供台達機電產品在RS-485連線、保護及應用非常方便的介面轉接器。 
ADP485-01
提供四種不同型式之插座以搭配台達機電產品  PLC DVP系列、人機介面  DOP系列、變頻器 
VFD
系列、伺服驅動器ASD系列使用,提供相互間  RS485通訊連線使用。 
  產品外觀 
32
6
60
3
1
0
6
,8
9
0
6
8
7
3,4
1
2
3
4
5
 
尺寸單位:mm 
固定板 
終端電阻選擇開關(出廠設定值為 OFF 
COM1 (DB9
母座) 
DIN
軌糟  (35mm) 
COM2 (DB9
公座) 
RS-485
連接口 
銘牌 
RJ12
連接口(連接變頻器) 
  選購連接線 
ADPCAB03A
:ADP485-01   台達伺服驅動器 ASD-A 連接線/30 公分 
ADPCAB03B
:ADP485-01   台達伺服驅動器 ASD-B 連接線/30 公分 
 
 
 
繁體中文 
 
台達機電產品 RS-485 網路連接圖 
ADP485-01 
 VFD 變頻器 
RS-485
網路
RJ12
VFD  Series
 
ADP485-01 
 DOP 人機介面 
RS-485
網路
F1
F3
F2
人機介面 DOP
COM1 COM2
對 1 接線
DB9
公頭
DB9
公頭
 
連接於 COM 1