Delta Electronics IFD9502 Leaflet

Page of 2
 
 
 
Warning 
 Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent 
damages on the device or injuries to staff. 
 Switch off the power before wiring. 
 This instruction sheet only provides introductory information on electrical specification, functions, wiring, 
trouble-shooting and peripherals for IFD9502. Details of DeviceNet protocol are not included in this sheet. For 
more information on DeviceNet Protocol, please refer to relevant reference or literatures. 
 IFD9502 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, 
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key 
or specific tools are required to open the enclosure) in case danger and damage on the device may occur. 
 IFD9502 is to be used for controlling the operating machine and equipment. In order not to damage it, only qualified 
professional staff familiar with the structure and operation of it can install, operate, wire and maintain it. 
 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power and DO NOT touch any terminal when the power is switched on. 
Make sure the ground terminal 
  is correctly grounded in order to prevent electromagnetic interference. 
 Introduction 
Thank you for choosing Delta IFD9502 DeviceNet Slave Communication Module. IFD9502 can be applied to 
the connection between DeviceNet and Delta’s programmable logic controllers, AC motor drives, servo drives, 
temperature controllers and human machine interfaces. In addition, IFD9502 offers custom function, which can 
be applied to the connection between DeviceNet and self-defined equipment with Modbus protocol. 
 Functions 
 Supports Group 2 only servers 
 Supports explicit connection in the pre-defined 
master/slave connection group 
 Supports polling 
 Supports EDS files in DeviceNet network 
configuration tools 
 Product Profile & Outline 
   
Unit: mm 
Communication port 
Address setup rotary switch 
Function setup DIP switch 
Instruction on function setup switch 
SP (Scan Port) indicator 
MS (Module Status) indicator 
NS (Network Status) indicator 
DeviceNet connector 
 
DIN rail 
 
DIN rail clip 
 
 Specifications 
 DeviceNet Connector 
Type 
Removable connector (5.08mm) 
Transmission method 
CAN 
Transmission cable 
2 communication cables, 2 power cables and 1 shielded cable 
Electrical isolation 
500V DC 
1
2
3
4
5
6
7
8
9
10
ENGLISH 
 Communication   
 
 
   
Message type 
I/O polling; explicit 
Series transmission 
speed 
125kbps; 250kbps; 500kbps 
Equipment type 
12 
Company ID 
799 (Delta Electronics, Inc.) 
 Electrical Specifications 
Voltage 
11 ~ 25V DC (offered by the power cable in the network) 
Current 
28mA (typical), 125mA impulse current (24V DC) 
 Environment
 
Standards 
IEC 61131-2, UL508 
Storage/Operation 
Storage: -25°C~70°C (temperature), 5~95% (humidity) 
Operation: 0°C~55°C (temperature), 50~95% (humidity); pollution degree 2 
Shock/Vibration 
immunity 
International Standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & 
IEC 68-2-27 (TEST Ea) 
Interference immunity 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz~1,000MHz, 1.4GHz~2GHz,10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
Certificates 
CE, UL 
 Installation & Wiring 
 Install IFD9502 in an enclosure with sufficient space around it to 
allow heat dissipation (see the figure). 
 DO NOT place the I/O signal wires and power supply wire in the 
same wiring circuit.
 
 
<1.5m m
28- 12AWG
 
 Use 28-12AWG (1.5mm) single or multiple core wire on I/O wiring terminals. 
See the figure for its specification. 
 The terminal screws shall be tightened to 4.75 kg-cm (4.12 in-lbs). 
 Use 60°C /75°C copper wires only.
 
 Components 
 DeviceNet Connector 
To connect to the DeviceNet network, use the connector enclosed with IFD9502 or any connectors you can 
buy in the store for wiring. 
PIN 
Signal 
Color 
Description 
V- 
Black 
0V DC 
CAN_L 
Blue 
Signal- 
SHIELD 
--- 
Shielded cable 
CAN_H 
White 
Signal+ 
V+ 
Red 
24V DC 
 
1
2
3
4
5
 
 Address Switch 
The two rotary address setup switches set up the node addresses on DeviceNet 
network in decimal form. Setup range: 00 ~ 63 (64 ~99 are forbidden) 
5
0
x10
1
0
x10
5
0
 
Example: 
If you need to set the node address of IFD9502 to 26, simply switch the corresponding rotary switch of X10
1
 to 
“2” and the corresponding rotary switch of X10
0
 to “6” 
Address Setting 
Description 
0…63 
Valid DeviceNet node address 
Others 
Invalid DeviceNet node address 
Note: The changed values on switches are only valid when IFD9502 is re-powered. When IFD9502 is operating, 
changing the set value of node address will be invalid.
 
 Function Switch 
The DIP switch is to be used on the equipment connected to IFD9502, the selection 
of communication ports and setting up the baud rate of IFD9502 and the Master 
station in DeviceNet. 
1 2 3 4 5 6 7 8
SW3
DIP
ON
 
 Selecting the Equipment Connected to IFD9502 
PIN1 
PIN2 
PIN3 
Equipment 
  PIN1 
PIN2 
PIN3 
Equipment 
ON 
OFF 
OFF 
AC motor drive 
  ON 
OFF 
ON 
Human machine interface 
OFF 
ON 
OFF 
PLC 
  OFF 
ON 
ON 
Custom equipment 
ON 
ON 
OFF 
Temperature controller 
  ON 
ON 
ON 
For internal system use 
OFF 
OFF 
ON 
Servo drive 
 
 
 
 
 
Example: 
If the equipment connected to IFD9502 is a Delta servo drive, you only need to switch PIN 3 to “ON”, PIN 1 and 
PIN 2 to “OFF” and re-power it. 
Note: The changed setting of the switch is only valid when IFD9502 is re-powered. When IFD9502 is operating, 
changing the setting of DIP switch will be invalid. 
 Selecting IFD9502 Communication Mode 
PIN4 
PIN5 
Communication Mode 
 
PIN4 
PIN5 
Communication Mode 
OFF 
OFF 
RS-485 
 
ON 
OFF 
Incorrect setting 
ON 
ON 
RS-232 
  OFF 
ON 
Incorrect setting 
Note: The changed setting of communication mode is only valid when IFD9502 is re-powered. When IFD9502 is 
operating, changing the setting of communication mode will be invalid. 
 Setting up Baud Rate 
PIN 6 
PIN7 
PIN8 
Baud Rate 
  PIN 6 
PIN7 
PIN8 
Baud Rate 
OFF 
OFF 
125kbps 
  OFF 
ON 
500kbps 
ON 
OFF 
Reserved 
250kbps 
 
ON 
ON 
Reserved 
Auto baud rate detection 
 Note: The changed setting of the baud rate of DeviceNet is only valid when IFD9502 is re-powered. When IFD9502 is 
operating, changing the communication speed will be invalid. 
 Communication Ports on IFD9502 
The communication ports on IFD9502 are used for the connection to equipment 
(Delta PLC, Delta AC motor drive, Delta temperature controller, Delta servo drive, 
Delta human machine interface and custom equipment) 
PORT1
PORT2
 
 PORT 1 
PORT 1 Sketch 
Terminal No. 
Description 
N.C. 
GND 
DATA- 
DATA+ 
N.C. 
1
2
3
4
5
6
PORT1
 
N.C. 
 Note: PORT 1 supports RS-485 communication mode only. 
 PORT 2 
PORT 2 Sketch 
Terminal No. 
RS-232 
RS-485 
N.C. 
N.C. 
RXD 
N.C. 
TXD 
DATA- 
N.C. 
N.C. 
GND 
GND 
N.C. 
N.C. 
N.C. 
N.C. 
N.C. 
DATA+ 
1
6
2
7
3
8
4
9
5
DB9  male
 
N.C. 
N.C. 
Note: PORT 2 supports RS-232 and RS-485 communication mode only. 
 LED Indicators & Troubleshooting 
There are 3 LED indicators on IFD9502, Network Status LED, Module Status LED and Scan Port LED, for 
displaying the connection status of the communication. 
 Network Status LED 
LED status 
Indication 
How to deal with it? 
OFF 
Device is not on-line. 
- The device has not completed the 
Dup_MAC_ID test yet. 
- The device may not be powered.   
1. Check the power of IFD9502 and see if the 
connection is normal. 
2. Check if the node communication on the 
BUS is normal. 
3. Make sure at least 1 node is normally 
communicating with the network through 
IFD9502. 
Green light flashes 
Device is on-line but has no connections 
in the established state. 
- The device has passed the 
Dup_MAC_ID test, is on-line, but has 
no established connections to other 
nodes. 
- This device is not allocated to a master. 
--- 
Green light ON 
The device is on-line and has 
connections in the established state. 
- The device is allocated to a Master. 
  --- 
Red light flashes 
I/O Connections are in the timed-out 
state. 
  --- 
LED status 
Indication 
How to deal with it? 
Red light ON 
Failed communication device. The device 
has detected an error that has rendered it 
incapable of communicating on the 
network (Duplicate MAC ID fail, or 
Bus-off). 
1. Make sure all the node addresses on the 
BUS are not repeated. 
2. Check if the network installation is normal. 
3. Check if the communication speed of 
IFD9502 is consistent with that of the BUS. 
4. Check if the station No. of IFD9502 is 
valid. 
5. Check if your choice of switch on IFD9502 
is consistent with the actual connected the 
equipment. 
6. Check if IFD9502 is correctly wired with 
the equipment. 
 Module Status LED 
LED status 
Indication 
How to deal with it? 
OFF 
There is no power applied to the device. 
Check the power of IFD9502 and see if the 
connection is normal. 
Green light flashes 
The device needs commissioning due to 
configuration missing, incomplete or 
incorrect. 
The device may be in the standby state. 
Green light ON 
The device is operating in a normal 
condition. 
Red light flashes 
Recoverable fault 
1.  Reset parameters in IFD9502. 
2.  Check if IFD9502 is correctly wired with 
the equipment. 
Red light ON 
The device has an unrecoverable fault; 
may need replacing. 
Send back to factory for repair. 
 Scan Port Status LED 
LED Status 
Indication 
How to deal with it 
OFF 
Power is off 
Check the power of IFD9502 and see if the 
connection is normal. 
Green light flashes 
IFD9502 is reading the preset value in 
the equipment. IFD9502 obtains the 
parameters from the equipment and 
initializes some of the attributes. 
  - 
Green light ON 
Communication between IFD9502 and 
the equipment is normal. 
  - 
Red light flashes 
CRC check fails, or the equipment sends 
back error information. 
1. Check if the communication format of the 
equipment is correctly set up. 
2. Check carefully if the installation is correct. 
Red light ON 
Connection fails, or no connection. 
1. Check if IFD9502 is correctly connected 
with the equipment. 
2. Restart the connection and make sure the 
communication cable meets the 
specification. 
 
注意事項 
 
使用前請務必仔細閱讀本使用手册,幷依照本手册指示進行操作,以免造成産品受損或人員受傷。 
 
配線時請務必關閉電源。 
 
本使用說明書僅提供電氣規格、功能規格、安裝配綫、故障排除及周邊裝置部分說明,本使用說明書僅作爲
IFD9502
操作指南和入門參考,DeviceNet 協定的詳細內容這裏不作介紹。如果讀者想瞭解更多 DeviceNet
協定的內容,請參閱相關專業文章或書籍資料。 
 
本機為開放型  (OPEN TYPE)  機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊∕衝
擊意外之外殼配線箱內。另必須具備保護措施  (如:特殊之工具或鑰匙才可打開)  ,防止非維護人員操作或意
外衝擊本體,造成危險及損壞。 
 
本産品用來控制運轉中的機械及設備。爲避免損壞本産品,只有合格且熟悉本産品結構及操作的專業人員才
可進行本產品之安裝、操作、配線及維護。 
 
交流輸入電源不可連接於輸入∕輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,且請
勿在上電時觸摸任何端子。本體上之接地端子 務必正確的接地,以提高產品抗雜訊能力。 
  產品簡介 
謝謝您使用台達 IFD9502 模組,IFD9502 定義爲 DeviceNet 從站通訊模組,可用于 DeviceNet 網路和台達可程
式控制器、台達變頻器、台達伺服驅動器、台達溫控器以及台達人機介面的連接。此外,IFD9502 還提供自定義
功能,該功能用於連接 DeviceNet 網路和符合 Modbus 協定的自定義設備。 
 支援的功能 
  支援  Group 2 only servers 
  在預定義的主/從連接組中支援顯性連接 
  支援輪詢連接 
  在 DeviceNet 網路配置工具中支援 EDS 文件檔 
 產品外觀及各部介紹 
   
尺寸單位: mm 
通訊口 
位址設定開關 
功能設定開關 
功能設定開關說明 
SP (Scan Port) 
指示燈 
MS (Module Status) 
指示燈 
NS (Network Status) 
指示燈 
DeviceNet
通訊連接器 
 
DIN
軌槽 
 
DIN
軌固定扣 
 
 
功能規格 
 DeviceNet 連接器 
接頭 
可插拔式連接  (5.08mm) 
傳輸方式 
CAN 
傳輸電纜 
2
條通訊線、2 條電源線、1 條遮蔽線 
電氣隔離 
500V DC 
1
2
5
6
7
8
10
繁體中文 
 
通訊 
   
 
   
資訊類型 
I/O
輪詢  顯性 
串列傳輸速率 
支援 125kbps; 250kbps; 500kbps(位元∕秒) 
設備類型 
12 
廠商 ID 
799
(台達電子) 
 
電氣規格 
電壓規格 
11 ~ 25V DC
(由網路中之電源線提供) 
電流規格 
28mA
(典型值),125mA 衝擊電流  (24V DC) 
 
環境規格 
標準 
IEC 61131-2,UL508 
標準 
操作∕儲存環境 
儲存:-25°C ~ 70°C(溫度),5 ~ 95%(濕度) 
操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度),污染等級 2 
耐振動∕/衝擊 
國際標準規範  IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 
(TEST Ea) 
雜訊免疫力 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 1.4GHz ~ 2GHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
認證項目 
CE
認證、UL 認證 
 
盤內安裝及配線 
 IFD9502
在安裝時,請裝配于封閉式之控制箱內,其周圍應保持
一定之空間(如右圖所示),以確保 IFD9502 散熱功能正常。 
 
在配線時請勿將輸入點信號綫與輸出點或電源等動力綫置于同一
綫糟內。
   
 
<1.5m m
28- 12AWG
 
 
輸出/入配綫端請使用 28-12AWG(1.5mm)單蕊祼綫或多蕊綫,端子規格如
左所示。 
 IFD9502
端子鏍絲扭力為 4.75 kg-cm(4.12 in-lbs)。 
 
只能使用 60°C/75°C 的銅導線。 
 
各部元件介紹 
 DeviceNet 通訊連接器 
與 DeviceNet 傳送線連接。可使用 IFD9502 隨機附帶的連接器或者市售的連接器進行配線。 
接腳 
信號 
顏色 
敘述 
V- 
黑色 
0V DC 
CAN_L 
藍色 
Signal- 
SHIELD 
遮蔽線 
CAN_H 
白色 
Signal+ 
V+ 
紅色 
24V DC 
 
1
2
3
4
5