Delta Electronics DVP-PLC Leaflet

Page of 2
 
 
 
Warning
 
 
This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & 
wiring. Other detail infromation about programming and intructions is compatible with SV series; please see PLC 
Application Manual. For more information about the optional peripherals, please see individual product instuction 
shee or “DVP-PLC Application Manual: Special module”. 
 
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric 
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the 
enclosure, in order to prevent hazard to users or damage the PLC. 
 
Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may damage the PLC. 
Check all the wiring prior to power up. To prevent any electromagnetic noise, make sure the PLC is properly 
grounded 
. Do NOT touch terminals when power on. 
 Introduction 
 Product Profile & Outline 
1
2
3
5
9
4
9
6
10
5
4
7
8
 
Open COM1 Cover 
 
 
 
  Communication port cover 
  Extension module connection port cover 
  I/O terminal cover 
  Input indicator 
  Function card/memory card cover 
  Output indicator 
  I/O terminals 
  DIN rail clip 
  I/O terminal No. 
  DIN rail (35mm) 
 
3
1
2
6
7
1
2
5
4
8
 
Open COM2 cover 
 
 
 
  Mounting screw 
  Memory card port 
  Direct mounting hole 
  POWER/RUN/BAT.LOW/ERROR indicator 
  Battery socket 
  Extension module connection port 
  Function card mounting hole 
 
 
 
ENGLISH 
Removable Terminal Block
COM 2 (RS-485)
RUN / STOP SWITCH
VR 0
VR 1
COM 1 (RS-232)
Ba ttery
 
Remove  RS-485 
terminal 
 
 
Part 
Description 
COM2 (RS-485) 
For both master & slave modes 
RUN/STOP switch 
PLC RUN/STOP control 
VR0 
Enable M1178/corresponding value of D1178 
VR1 
Enable M1179/corresponding value of D1179 
COM1 (RS-232) 
For slave mode 
Battery 
Shall be changed within 1 min. 
 
 Dimension 
4.6 X
2
W
W1
8
0
.0
9
0
.0
82.2
 
 
Model 
W (mm) 
W1 (mm) 
DVP16EH00R2/T2 
113 
103 
DVP20EH00R2/T2 
113 
103 
DVP32EH00R2/T2 
143.5 
133.5 
DVP40EH00R2/T2 
158.8 
153.8 
DVP48EH00R2/T2 
174 
164 
DVP64EH00R2/T2 
212 
202 
DVP80EH00R2/T2 
276 
266 
 
 Specifications 
 
 
Model 
Item
 
16EH00
2  20EH00
2  32EH00
2  40EH00 
2  48EH00
2  64EH00
2  80EH00
Power supply 
voltage 
100 ~ 240V AC (-15% ~ 10%); 50/60Hz ± 5% 
Fuse capacity 
2A/250V AC 
Power consumption 
50VA 
50VA 
60VA 
60VA 
60VA 
80VA 
80VA 
DC24V current 
supply 
500mA 
500mA 
500mA 
500mA 
500mA 
500mA 
500mA 
Power protection 
DC24V; output short-circuited 
Withstand voltage 
1,500V AC (Primary-Secondary); 1,500V AC (Primary-PE); 500V AC (Secondary-PE) 
Insulation 
resistance 
> 5 MΩ (all I/O point-to-ground: 500V DC) 
Noise immunity 
ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 
250V; Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 
Earth 
The diameter of grounding wire shall not be less than that of L, N terminal of the power. (When 
many PLCs are in use at the same time, please make sure every PLC is properly grounded.) 
Operation/storage 
Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2 
Storage: -40 ºC ~ 70 ºC (temperature); 5 ~ 95% (humidity) 
Vibration/shock 
immunity 
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27  (TEST 
Ea) 
Weight (g) 
500/480 
520/500 
652/612 
710/675 
748/688 
836/756 
948/848 
 Input Point Specification 
24VDC single common port input 
Spec. 
Items 
Low speed   
High speed (200KHz) 
Note 
Input wiring type 
Change wiring from S/S to SINK or SOURCE 
Input indicator 
LED display; light on = ON, light off = OFF 
Input voltage 
24VDC 
Off  On 
X0 ~ X7, X12, X13, X16, X17, X20 ~ X47: >
 18.5V DC 
X10, X11, X14, X15: >
 16.5V DC 
Active 
Level 
On  Off 
X0 ~ X47: <
 8V DC 
Response time/ 
noise immunity 
10ms 
0.5us 
Input point X0 ~ X7, X10 ~ X17 
can conduct 10 ~ 60ms digital 
filter adjustment 
 Output Point Specification 
Single common port transistor output 
Spec. 
Items 
Low speed   
High speed* 
Single common port relay 
output 
Max. frequency 
10KHz 
200KHz 
Load ON/OFF control 
Output indicator 
LED display; light on = ON, light off = OFF 
Min. load 
2mA/DC power supply 
Working voltage 
5 ~ 30VDC 
<250V AC, 30V DC 
Insulation 
Photocoupler isolation 
Magnetic isolation 
Current 
specification 
0.3A/1 point @ 40ºC 
<1KHz, 0.3A/1 point @ 40°C 
≧1KHz, 30mA/1 point @ 40°C 
2A/1 point (5A/COM) 
75VA (conductive), 90W 
(resistive) 
Off  On: 20us 
Max. output delay 
time 
On  Off: 30us 
0.2us 
10ms 
Over-current 
protection 
N/A 
Mechanical life 
N/A 
2×10
7
 times (without load) 
Electrical life 
N/A 
1.5×10
5
 times (5A 30V DC); 
5×10
5
 times (3A 120V AC); 
3×10
4
 times (5A 250V AC) 
*High-speed output points (Y0, Y2) are only in DVP20EH2 and DVP32EH2; high-speed output points (Y0, Y1, Y2, Y3, Y4, Y6) are 
only in DVP40EH2. 
 Installation & Wiring 
3.1 PLC Mounting Arrangements and Wiring Notes 
How to install DIN rail: 
DVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and 
7.5mm in depth. When mounting PLC to DIN rail, be sure to use the end bracket to stop 
any side-to-side movement of PLC and reduce the chance of wires being loosen. A small 
retaining clip is at the bottom of PLC. To secure PLC to DIN rail, place the clip onto the 
rail and gently push it up. To remove it, pull the retaining clip down and gently remove 
PLC from DIN rail, as shown in the figure. 
How to screw: Please use M4 screw according to the dimension of the product. 
 
D VP MPU
> 50mm
> 50mm
> 50mm
> 50mm
 
Please install PLC in an enclosure with sufficient space around it to allow heat 
dissipation as shown in the figure.
 
Wiring: 
To suit  M3.5 screw  terminals
Below 6.2
Below 6.2
 
1. Use O-type or Y-type terminal. See the figure in the left hand side for its 
specification. PLC terminal screws should be tightened to 5 ~ 8 kg-cm (4.3 ~ 
6.9 in-Ibs) and please use only 60/75ºC copper conductor. 
2. DO NOT wire empty terminal    •  . DO NOT place the input signal cable and 
output power cable in the same wiring circuit. 
3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring. 
Tear off the sticker on the heat dissipation hole for preventing alien 
substances from dropping in, to ensure normal heat dissipation of the PLC. 
3.2 Wiring Notes 
 Power Input Wiring 
The power input of DVP-EH series is AC. When operating the PLC, please make sure that: 
1.  The input voltage should be current and its range should be 100 ~ 240V AC. The power should be 
connected to L and N terminals. Wiring AC110V or AC220V to +24V terminal or input terminal will result in 
serious damage on the PLC. 
2.  The AC power input for PLC MPU and I/O extension modules should be ON or OFF at the same time. 
3.  Use wires of 1.6mm (or longer) for the grounding of PLC MPU. The power shutdown of less than 10 ms will 
not affect the operation of the PLC. However, power shutdown time that is too long or the drop of power 
voltage will stop the operation of the PLC and all outputs will go OFF. When the power supply turns normal 
again, the PLC will automatically return to its operation. Please be aware of the latched auxiliary relays and 
registers inside the PLC when programming. 
AC Power Input 
L
   
2.0 A
DC/DC
 
+5V
 
+24V
 
24G
 
S/S
 
X0
 
X1
 
X2
 
100~240VAC
 
 
0.5A is the maximum power supply for +24V power supply output terminal. DO NOT connect other 
external power supplies to this terminal. Every input terminal requires 6 ~ 7mA to be driven; e.g. the 
16-point input will require approximately 100mA. Therefore, +24V cannot give output to extermal load 
that is more than 400mA. 
 Safety Wiring 
Since a PLC controls many devices, actions of any device may affect actions of other devices, and the 
breakdown of any one device may cause the breakdown of the whole auto-control system and danger. 
Therefore, we suggest you wire a protection circuit at the power input terminal, as shown in the figure below. 
 
  AC power supply load 
  Power circuit protection fuse (3A) 
  Power indicator 
  Emergency stop 
This button can cut off the system power supply when accidental 
emergency takes place.   
  System circuit isolation device 
The device is made of electromagnetic contactor and relay as the 
switch to prevent the instability of system when the power is 
intermittently supplied.   
  DVP-PLC (main processing unit) 
  Earth 
M C
MC
N
L
1
1
2
3
4
5
6
7
8
G u ar d
L im it
MC
 
  Power supply AC: 100 ~ 240V AC 
 Input Point Wiring 
There are two types of DC inputs, SINK and SOURCE. 
Input point loop equivalent circuit 
Wiring loop 
DC Signal IN 
S/S
X0
Sinking
 
SINK mode 
(common port for current 
input S/S) 
24VDC
24G
X0
S/S
+24V
SINK
+5V
 
24G
S/S
X0
X1
X2
+24V
Sink  Type
 
 
Input point loop equivalent circuit 
Wiring loop 
DC Signal IN 
S/S
X0
Sourcing
 
SOURCE mode 
(common port for current 
output S/S) 
24VDC
24G
X0
S/S
+24V
SOURCE
+5V
 
24G
S/S
X0
X1
X2
+24V
Source Type
 
 Output Point Wiring 
Relay (R) contact circuit wiring 
Y0
RY
LED
C0
LOAD
POWER
DVP-**-**-**-R
RELAY OUTPUT
 
2
3
1
5
C0
Y0
Y1
C1 Y3 Y4 C2 Y6 Y7
4
MC1
MC2
7
10
3
2
8
9
6
 
 
  Flywheel diode: To extend the life span of contact 
  Emergency stop: Uses external switch 
  Fuse: Uses 5 ~ 10A fuse at the common port of output contacts to protect the output circuit.   
  Varistor: To reduce the interference on AC load 
  Empty terminal: not in use 
  DC power supply 
  Neon indicator 
  AC power supply 
  Incandescent light (resistive load) 
  Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC internal 
program, to ensure safety protection in case of any unexpected errors.   
Transistor (T) contact circuit wiring 
Y0
LED
C0
TRANSISTOR OUTPUT
LOAD
DVP-**-**-**-T
<  0.5A
 
M C1
M C 2
2
3
1
C0 Y 0
Y 1 C1 Y 4 Y 5 Y 6
Y 7
5
4
5
3
4
 
 
  DC power supply 
  Emergency stop 
  Circuit protection fuse 
  Flywheel diode + inductive load 
  Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC internal 
program, to ensure safety protection in case of any unexpected errors. 
 
注意事項 
 
本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計及指令與
SV
系列相容,
詳細說明請見
DVP-PLC
應用技術手冊【程式篇】,選購之週邊裝置詳細說明請見該產品隨機手冊或
DVP-PLC
應用技術手冊【特殊模組篇】。
 
 
本機為開放型
  (OPEN TYPE) 
機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊
/
衝擊
意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。
 
 
交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子
 
 
務必正確的接地,可提高產品抗雜訊能力。
 
  產品簡介 
 
產品外觀及各部介紹 
1
2
3
5
9
4
9
6
10
5
4
7
8
 
COM1
上蓋打開 
 
 
 
  通訊口上蓋 
  擴充機連接口上蓋 
  輸出/入端子蓋 
  輸入點指示燈 
  功能卡/記憶卡上蓋 
  輸出點指示燈 
  輸出/入端子 
  DIN 軌固定扣 
  輸入/輸出端子編號 
  固定 DIN 軌糟  (35mm) 
 
3
1
2
6
7
1
2
5
4
8
 
COM2
上蓋開啟 
 
 
  機身固定螺絲 
  記憶卡插槽 
  直接固定孔 
  電源、運行、錯誤及電池狀態指示 
  電池插槽 
  擴充機連接口 
  功能卡固定孔 
 
繁體中文
繁體中文
繁體中文
繁體中文    
脫落式端子
COM 2 (RS-485)
RUN / STOP 
開關
VR 0
VR  1
COM 1 (RS-232)
電池
 
RS-485
端子取出 
 
 
部  位 
說  明 
COM2 (RS-485) 
Master/Slave
模式兩用 
RUN/STOP
開關 
PLC RUN/STOP
控制 
VR0 
M1178
啟動/D1178 對應值 
VR1   
M1179
啟動/D1179 對應值 
COM1 (RS-232) 
Slave
模式使用 
電池 
更換電池時,必須在 1 分鐘內完成。 
 
 
外觀及尺寸 
4.6 X
2
W
W1
8
0
.0
9
0
.0
82.2
 
 
機  種  型  號 
W (mm) 
W1 (mm) 
DVP16EH00R2/T2 
113 
103 
DVP20EH00R2/T2 
113 
103 
DVP32EH00R2/T2 
143.5 
133.5 
DVP40EH00R2/T2 
158.8 
153.8 
DVP48EH00R2/T2 
174 
164 
DVP64EH00R2/T2 
212 
202 
DVP80EH00R2/T2 
276 
266 
 
  電氣規格 
 
   
機種 
項目 
16EH00
2  20EH00
2  32EH00
2  40EH00
2  48EH00
2  64EH00
2  80EH00
電源電壓 
100 ~ 240V AC (-15% ~ 10%); 50/60Hz ± 5% 
電源保險絲容量 
2A/250V AC 
消耗電力 
50VA 
50VA 
60VA 
60VA 
60VA 
80VA 
80VA 
DC24V
供應電流 
500mA 
500mA 
500mA 
500mA 
500mA 
500mA 
500mA 
電源保護 
DC24V
輸出具短路保護 
突波電壓耐受量 
1,500V AC (Primary-Secondary); 1,500V AC (Primary-PE); 500V AC (Secondary-PE) 
絕緣阻抗 
5 M
Ω以上  (所有輸出/入點對地之間  500VDC) 
雜訊免疫力 
ESD:  8KV Air  Discharge;  EFT: Power Line:  2KV, Digital  I/O:  1KV, Analog  & Communication  I/O: 
250V; Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 
接地 
接地配線之線徑不得小於電源端 L, N 之線徑(多台 PLC 同時使用時,請務必單點接地) 
操作/儲存環境 
操作:0°C ~55°C(溫度),50 ~ 95%(濕度),污染等級 2; 
儲存:-40°C ~70°C  (溫度),5 ~ 95%(濕度) 
耐振動/衝擊 
國際標準規範  IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
重量  (約), (g) 
500/480 
520/500 
652/612 
710/675 
748/688 
836/756 
948/848 
 
輸入點規格 
24V DC
單端共點輸入
單端共點輸入
單端共點輸入
單端共點輸入 
規格 
項目 
低速 
高速 200KHz 
備註
備註
備註
備註 
輸入接線型式 
由端子 S/S 變換接線為 SINK 或 SOURCE 
輸入動作指示 
LED
顯示;燈亮表示為 ON,不亮表示為 OFF 
輸入信號電壓 
24V DC 
Off 
 On 
X0 ~ X7, X12, X13, X16, X17, X20 ~ X47: >
 18.5V DC 
X10, X11, X14, X15: >
 16.5V DC 
動作位準 
On 
 Off 
X0~X47: <
 8V DC 
反應時間/雜訊抑制 
10 ms 
0.5us 
輸入點 X0  ~  X7、X10  ~ 
X17
可作 10 ~ 60 ms 數位
濾波調整