Warning 
 This instruction sheet only provides introductory information on electrical specification, installation and wiring. 
 Switch off the power before wiring. DO NOT touch any terminal when the power is switched on. 
 IFD9507 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, 
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key 
or specific tools are required to open the enclosure) in case danger and damage on the device may occur. 
 
 Introduction 
 Features 
1.  Auto-detects 10/100 Mbps transmission  speed; MDI/MDI-X auto-detection. 
2.  The monitor table temporarily stores the monitored data for the user to fast save or acquire the data. 
3.  Supports Modbus TCP protocol and
 
Ethernet/IP protocol (supports Master and Slave mode).   
4.  Able to send out emails after being triggered. 
5.  The station address, RS-485 communication format and baud rate can be set up externally. 
6.  The communication parameters can be set up through Web. 
 Product Profile & Outline 
9
 
 
 
Communication  ports: RS-485, 
Ethernet, RS-232
 
Power  indicator
 
Address switch
 
Data  format/baud  rate switch
 
Digit  display
 
RS-485 indicator, Reset button, 
Ethernet indicator
 
Module  name
 
RS-485 connector, digital input 
points, power input point, earth point
 
DIN rail connector
 
 
 
 Specifications 
 Ethernet Interface 
Interface 
RJ-45 with Auto MDI/MDIX 
Transmission method 
Ethernet Type II 
Transmission  cable 
Category 5e, 100m (Max) 
Transmission  speed 
10/100 Mbps Auto-Detection 
Network  protocol 
ICMP, IP, TCP, UDP, DHCP, SMTP, Modbus OVER TCP/IP, Ethernet/IP, Delta 
Configuration 
 
ENGLISH 
 RS-485 Connector 
Interface 
RJ-11 
Transmission  method 
RS-485 
Transmission  speed 
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 
Communication format 
Stop bit: 1, 2    Parity bit: None, Odd, Even    Data bit: 7, 8    ASCII/RTU 
Communication 
protocol 
Modbus, User Define 
 RS-232 Connector 
Interface 
Mini Dim 
Transmission  method 
RS-232 
Transmission  speed 
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 
Communication format 
Stop bit: 1, 2    Parity bit: None, Odd, Even    Data bit: 7, 8    ASCII/RTU 
Communication 
protocol 
Modbus, Delta Configuration, User Define 
Transmission  cable 
DVPACAB215/DVPACAB230/DVPACAB2A30 
 Terminal Block 
Interface 
Feed-through  terminal 10PIN 
Transmission  method 
RS-485 
Transmission  distance 
1,200m 
Transmission  speed 
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 
Communication format 
Stop bit: 1, 2    Parity bit: None, Odd, Even    Data bit: 7, 8    ASCII/RTU 
Communication 
protocol 
Modbus, User Define 
 Electrical Specifications
 
Power  voltage 
24V DC (-15% ~ 20%) supplied  by  feed-through  terminal 
Power  consumption 
3W 
Insulation  voltage 
500V
 
Weight 
140g 
 Environment
 
Noise immunity 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV, 
Communication I/O: ±2KV 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz, 
10V/m 
Conducted Susceptibility Test (EN 61000-4-6, IEC 61131-2 9.10): 150kHz ~ 
80MHz, 3V/m 
Surge Test (Biwave IEC 61132-2, IEC 61000-4-5): 
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM 
Operation/storage 
Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity),  pollution  degree 2 
Storage: -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity) 
Vibration/shock 
immunity 
International  standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 
68-2-27(TEST Ea) 
Certificates 
 
 
 Installation 
 Dimension 
 
Unit: mm 
 Address Switch 
Switch setting 
Content 
01 … F7 
Valid Modbus communication  address 
 
 Data Format Switch 
Switch setting 
Format 
  Switch setting 
Format 
7-N-1 
 
7-N-2 
8-N-1 
 
8-N-2 
7-O-1 
 
7-O-2 
8-O-1 
 
8-O-2 
7-E-1 
 
7-E-2 
8-E-1 
 
8-E-2 
 
 Baud Rate Switch 
Switch setting 
Baud  rate (bps) 
  Switch setting 
Baud rate (bps) 
110 
 
4,800 
150 
 
9,600 
300 
 
19,200 
600 
 
38,400 
1,200 
 
57,600 
2,400 
 
115,200 
 
 RJ-11 PIN  Definition 
PIN 
Signal 
Definition 
  PIN 
Signal 
Definition 
-- 
N/C 
 
D- 
Negative  pole for  data 
-- 
N/C 
 
GND 
Ground 
D+ 
Positive pole for data   
-- 
N/C 
 
 RJ-45 PIN Definition 
PIN 
Signal 
Definition 
  PIN 
Signal 
Definition 
Tx+ 
Positive pole for data 
transmission 
 
-- 
N/C 
Tx- 
Negative  pole for  data 
transmission 
 
Rx- 
Negative  pole for  data 
receiving 
Rx+ 
Positive  pole for data 
receiving 
 
-- 
N/C 
-- 
N/C 
 
-- 
N/C 
 
 RS-232 PIN  Definition 
PIN 
Signal 
Definition 
  PIN 
Signal 
Definition 
-- 
N/C 
 
Tx 
Transmission data 
-- 
N/C 
 
-- 
N/C 
-- 
N/C 
 
-- 
N/C 
Rx 
Reception  data 
 
GND 
Ground 
 
 Feed-through Terminal PIN Definition 
PIN 
Signal 
Definition 
SG 
Ground of signal 
D- 
Data- 
D+ 
Data+ 
X2 
Digital input 2 
X1 
Digital input 1 
X0 
Digital input 0 
S/S 
Ground of digital input 
24V 
+24V 
0V 
0V 
10 
-- 
Earth ground 
 
 LED Indicators & Trouble-Shooting 
There are 3 LED indicators and a digital display on IFD9507. POWER indicator displays the status of the 
working power. RS-485 and LINK/ACT indicators display the connection status of the communication. The 
digital display shows the address of and errors in IFD9507 and the error messages from the slave. 
 POWER LED 
LED status 
Indication 
How to correct 
OFF 
Working power is abnormal 
Check if the working power of IFD9507 is normal. 
Green light ON  Working power is normal 
-- 
 RS-485 LED 
LED status 
Indication 
How to correct 
OFF 
No communication or RS-485 
connection is abnormal. 
1. If the LED is off during the communication, check if the RS-485 in 
IFD9507 is normally connected. 
2. Check at least 1 node on the network is communicating normally. 
Constantly ON 
Abnormal RS-485 connection 
Switch D+ and D- 
Green light 
flashes 
RS-485 connection is normal. 
-- 
 LINK/ACT LED 
LED status 
Indication 
How to correct 
OFF 
No power, or no network 
connection 
1. Check the power of IFD9507 and make sure the network 
connection is normal. 
2. Re-power IFD9507. If the error still exists, send your IFD9507 
back to the factory for rep
a$ir. 
Green light ON 
The connection is normal, but no 
data transmission. 
-- 
Green light 
flashes 
The data transmission is normal.  -- 
 Codes in Digital Display 
Code 
Indication 
How to correct 
01 ~ F7 
The node address of IFD9507 when 
in normal operation 
-- 
F0 
Returning to default setting 
-- 
F1 
IFD9507 is booting. 
-- 
F2 
Working power in low voltage 
Check if the working power is normal. 
F3 
Internal memory error 
1.  Re-power IFD9507. If the error still exists, try step 2. 
2.  Reset IFD9507. If the error still exists, send it back to the factory 
for repair. 
F4 
Internal error caused by 
manufacturing in the factory 
1.  Re-power IFD9507. If the error still exists, try step 2. 
2.  Reset IFD9507. If the error still exists, send it back to the factory 
for repair. 
F5 
Network connection error 
Check if IFD9507 is normally connected to the network. 
F6 
Full number of devices connected in 
the network 
Check if the number is too much. 
F7 
UART setting error. 
Check if the RS-485, RS-232 communication format is correct. 
E1 
Alarm 1 triggered 
Check Alarm Input Point 1 
E2 
Alarm 2 triggered 
Check Alarm Input Point 2 
E3 
Alarm 3 triggered 
Check Alarm Input Point 3 
01 
Incorrect Modbus function 
Check if the Modbus instruction is correct. 
02 
Incorrect address 
Check if the Modbus instruction is correct. 
03 
Incorrect data 
Check if the Modbus instruction is correct. 
04 
CRC error 
1. Check if IFD9507 and RS-485 is connected normally. 
2. Check if the series transmission speed is consistent with that of 
other nodes on the network. 
0B 
No response from the station 
1. Check if IFD9507 and RS-485 is connected normally. 
2. Check if the series transmission speed is consistent with that of 
other nodes on the network. 
 
 
注意事項 
 
此安裝手冊只提供電氣規格、一般規格、安裝及配線等。 
 
配線時請務必關閉電源,請勿在上電時觸摸任何端子。 
 
本機為開放型  (OPEN  TYPE)  機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊∕
衝擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開),防止非維護人員操作
或意外衝擊本體,造成危險及損壞。 
  產品簡介 
  功能特色 
1. 
自動偵測 10/100 Mbps 傳輸速率,MDI/MDI-X 自動偵測。 
2. 
提供 Monitor table 可暫存監控的資料,讓使用者快速存取。 
3. 
支援 Modbus TCP  協定和 Ethernet/IP 協定(支援 Master 和 Slave 模式)。 
4. 
經觸發後發送電子郵件。 
5. 
可由外部設定站號、RS-485 通訊格式、鮑率。 
6. 
可由 Web 設定通訊參數。 
  產品外觀 
1 
通訊口 RS-485, Ethernet, 
RS-232 
2 
電源指示燈 
3 
站號設定開關 
4 
通訊格式、通訊速率設定開關 
5 
數位顯示器 
6 
RS-485
指示燈、Reset 按鍵、
Ethernet
指示燈 
7 
模組名稱 
8 
端子台 RS-485 連接器、數位輸
入點、電源輸入、大地 
9
 
9 
DIN
軌連接器 
  功能規格 
 Ethernet 連接器 
接頭 
RJ-45 with Auto MDI/MDIX 
傳輸方式 
Ethernet Type II 
傳輸電纜 
Category 5e, 100
公尺  (Max) 
傳輸速率 
10/100 Mbps Auto-Detection 
網路協定 
ICMP, IP, TCP, UDP, DHCP, SMTP, Modbus OVER TCP/IP, Ethernet/IP, Delta 
Configuration 
 
繁體中文 
 RS-485 連接器 
接頭 
RJ-11 
傳輸方式 
RS-485 
傳輸速率 
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 
通訊格式 
Stop bit: 1, 2    Parity bit: None, Odd, Even    Data bit: 7, 8    ASCII/RTU 
通訊協定 
Modbus, User Define 
 RS-232 連接器 
接頭 
Mini Dim 
傳輸方式 
RS-232 
傳輸速率 
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 
通訊格式 
Stop bit: 1, 2    Parity bit: None, Odd, Even    Data bit: 7, 8    ASCII/RTU 
通訊協定 
Modbus, Delta Configuration, User Define 
傳輸電纜 
DVPACAB215/DVPACAB230/DVPACAB2A30 
  端子台連接器 
接頭 
歐式端子台 10PIN 
傳輸方式 
RS-485 
傳輸距離 
1,200m 
傳輸速率 
110/150/300/600/1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 
通訊格式 
Stop bit: 1, 2    Parity bit: None, Odd, Even    Data bit: 7, 8    ASCII/RTU 
通訊協定 
Modbus, User Define 
  電氣規格
 
電源電壓 
24V DC (-15% ~ 20%) 
由歐式端子台輸入 
消耗電力 
3W 
絕緣電壓 
500V 
重量 
140g 
  環境規格
 
雜訊免疫力 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV, 
Communication I/O: ±2KV 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m 
Conducted Susceptibility Test (EN 61000-4-6, IEC 61131-2 9.10): 150kHz ~ 80MHz, 
3V/m 
Surge Test (Biwave IEC 61132-2, IEC 61000-4-5): 
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM 