 D8125INV 
 Installation 
 
 D8125INV Operation and Installation Guide  
 
© 2005 Bosch Security Systems 
Page 17 
49690E  
 
3.6.1.1 Point 
Mode 
The Point Mode setting determines whether: 
 
the transmitter is a burg point or fire point,  
 
Normally Open or Normally Closed contacts are used,  
 
the Internal and/or external contacts are used, and  
 
end of line resistors are used on the external contacts. 
This applies to RF Transmitters that have external contacts and/or internal magnetic contacts (see Table 7). 
External Contact 
Inovonics 
Transmitter 
Mode 
Normally 
Open 
Normally 
Closed 
End of Line Resistor 
(use 2.2 K ¼ Watt) 
Internal 
Contact 
Fire 
Point 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
10 
 
 
FA210 Reduced 
Size Universal 
 
FA210W 
 
FA250 High Power 
Universal 
 
FA210BN 
 
FA210WBN 
11 
 
 
 
 
 
 
 
FA210W & 
FA210WBN 
Reduced Size 
“Wide-Gap” 
Universal 
12  
 
 
 
Inovonics Transmitter 
Mode 
FA113 Keyfob  
(see Section 3.6.1.6 Programming the FA113 Keyfob, p. 22) 
FA202 Photoelectric Smoke Detector 
FA203S/D Necklace Pendant 
FA204 Pendant 
FA205S/FA205D Belt Clip/Loop 
FA206  ALL 
FA207 Glassbreak 
FA209 Billtrap 
FA216L/H Low Temperature/High Temperature  
FA223S/D Single/Double Button Water Resistant Pendant 
FA570 High Power Indoor Repeater 
FA575 High Power Outdoor Repeater 
4  
Table 6: Recommended Mode Values