Lopi Masonry Fireplace Factory Built (Metal) Fireplace Mobile Home Model: Pioneer Bay (Heritage Bay PI) User Manual

Page of 38
Installation
7
Travis Industries
4 0 5 1 2 1 6
9 3 5 0 8 0 5 1
Clearances
Insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the heater.
Insert must be placed a minimum 9" from a side wall (or combustible protruding more than
3/4").
Mantel Requirements
The mantel (combustible or non-combustible) must be a minimum13" above the hopper
lid (NOTE: measure clearance to the location where the mantel protrudes 3/4" or greater).
Hearth Requirements
The non-combustible hearth must extend 6" to the front and 6" to each side of the insert
(measure to the hopper lid).
Facing Requirements
The non-combustible facing must extend 6" to the side and 10" above  the hopper lid.
Placing the Insert
The insert must be placed within an undamaged masonry or factory built (metal) fireplace.
Loose bricks or other damage must be fixed.  Clean the fireplace before installing.
A 3/8" gap must be allowed between the surround panels and the face of the fireplace.
Run the power cord to the side 
along the front of the fireplace 
(do not route it under the insert).
The vent should 
be routed to the 
fireplace prior to 
installing the 
insert.  See the 
section "Vent 
Installation" for 
details on vent 
location.
Use the leveling bolts for 
fireplaces with recessed floors 
(included with the insert).  
Screw them into the baseplate 
from below.
The insert must protrude 9-3//8" 
onto the hearth for the panels to 
fit correctly.
9-3/8"
Apply the "This fireplace has been 
altered..." sticker to the fireplace.  You 
may wish to place it in a location where it 
will be covered by the surround panels.