Sierra Monitor Corporation 1260 Series Leaflet

Page of 2
1991 Tarob Court, Milpitas, CA USA 95035 Phone:  408-262-6611 Fax: 408-262-9042
(800) 727-4377         Email: sierra@sierramonitor.com            www.sierramonitor.com
ACCESSORIES
ACCESSORIES
SAMPLE DRAW PRODUCTS
Sample draw products are used in applications in which
the sensor cannot be installed directly at the gas sensing
location due to poor accessibility or the harshness of the
environment.  Sample is continuously drawn from the sens-
ing location to the sensor at a more suitable location.
The primary component of the sample draw product is a
venturi manifold that uses a continuous flow of driver air to
pull a slight vacuum through the sample supply line draw-
ing the sample into the manifold cavity connected to the
sensor.
5399-01 Sample Draw Fitting
The  sample  manifold  assembly  is  the  5399-01  Sample
Draw Fitting.  Sample stream draw and flow control is pro-
vided by the user.
5398-01 Sample Draw Assembly
The 5398-01 is a complete sample draw assembly includ-
ing the sample draw fitting, driver air, sample and exhaust
fittings and flow metering assembly.  This allows accurate
adjustment of sample flow using the signal flow meter lo-
cated on the flow metering assembly.
5398-02 Sample Draw/Dilution Assembly
The 5398-02 is used in applications in which the expected
gas concentration is either higher than the maximum range
of the sensor or sufficiently high to significantly reduce sen-
sor  life  with  extended  exposure.   This  assembly  adds  a
second flow meter for control of dilution air.  Adjustment of
sample and dilution air flow meters determines the dilu-
tion ratio.  Concentrations displayed on the Sentry Con-
troller must then be multiplied by the dilution factor to ar-
rive at actual concentrations.
SENSOR MOUNTING PRODUCTS
5311-00 Rainshield
The Rainshield is mounted over the sensor head to pro-
tect  the  sensor  from  direct  exposure  to  rain,  hosedown
and other splashing liquids.
5394-00 Duct Mount Fitting
The  Duct  Mount  Fitting  facilitates  installation  of  the  gas
sensor module onto an air duct.  The fitting also includes
the 5360-00 calibration gas delivery fitting so that calibra-
tion gas can be delivered to the sensor with out removing
the module from the duct.
CALIBRATION ADAPTERS
The Sentry system is designed for easy calibration of the
sensor modules.  The standard calibration adapter screws
over the head of the sensor.  Then calibration gas is fed
through a tube connected onto the adapter.
Magnetic  calibration  adapters  are  commonly  used  with
Sentry  gas  sensor  modules.    The  magnetic  calibration
adapter is used to control a switch inside the sensor mod-
ule.  When  the  adapter  is  first  applied  to  the  sensor  the
switch  closes  to  indicate  the  start  of  calibration  and  the
zero gas stage.  The second time the adapter is applied to
the module, the switch closure indicates that span gas is
being  applied.  When  the  magnetic  adapter  is  removed,
the module knows that calibration is complete and sends
the appropriate signal to the controller.
5398-01
5360-00
5394-00
© 2002 Sierra Monitor Corporation
ACCESSORIES
22009_Accessories_v2
12/18/02, 12:33 PM
2