SECTION 5: DUCT HEATER INSTALLATION
5.1 General 
To connect the inlet and outlet ducts to the heater, 
Duct-Mate or similar flanges may be slid over the 
duct connector flanges supplied on the unit and 
secured with screws. The connection to the duct 
then can be made using the Duct-Mate clips. The 
ducts must have removable access panels 
upstream and downstream of the heater. These 
panels must be of appropriate size and placement 
so that smoke or reflected light could be observed to 
indicate the presence of leaks in the heat 
exchanger. Covers for these openings should be 
sealed to prevent leakage.
Any transition into the inlet of the heater should be 
smooth, with a taper of no more than 15°. If elbows 
are required, they should be of either broad radius 
or fitted with properly designed air turns. Consult a 
professional to ensure air turns are properly 
designed.
The heater must be installed on the positive 
pressure side of the circulating air blower. Air flow 
through the heater must be as shown on Page 7, 
Figure 2
 and may not be reversed. The air flow must 
be adjusted such that it is within the acceptable 
range shown on Page 7, Section 5.1.2. The minimum 
inlet duct lengths shown on Page 7, Section 5.1.1 
must be observed. Pressure drop through the heat 
exchanger at various air flows is shown on Page 7, 
Section 5.1.2
.
Figure 2: Air Flow Direction
5.1.1 Minimum Inlet Duct Length
5.1.2 Temperature Rise and Pressure Drop Ranges
Model
Duct Length
Duct Size (W X H)
UHD[X][S][R] 150-175
52" (132 cm)
28" x 24" (71 cm x 60 cm)
UHD[X][S][R] 200-250
60" (162 cm)
28" x 32 1/4" (71 cm x 103 cm)
UHD[X][S][R] 300-400
75" (190 cm)
28" x 40 1/2" (71 cm x 82 cm)
UHD[X][S][R] 150
UHD[X][S][R]  175
UHD[X][S][R]  200
UHD[X][S][R]  225
Airflow
(CFM)
Temperature 
Rise (°F)
Pressure 
Drop 
(in wc)
Airflow
(CFM) 
Temperature 
Rise (°F)
Pressure 
Drop  
(in wc)
Airflow
(CFM)
Temperature 
Rise (°F)
Pressure 
Drop  
(in wc)
Airflow
(CFM)
Temperature 
Rise (°F)
Pressure 
Drop  
(in wc)
1,360
83
0.02
1,400
95
0.03
2,050
73
0.025
2,100
80
0.035
1,950
58
0.035
2,180
62
0.06
2,600
58
0.035
2,800
61
0.052
2,800
41
0.057
3,244
42
0.10
3,600
42
0.056
4,600
37
0.110
3,700
31
0.083
4,370
31
0.15
5,500
28
0.100
6,230
27
0.167
4,700
24
0.12
5,160
27
0.19
6,570
23.5
0.129
7,400
23
0.214
5,800
20
0.16
6,850
20
0.29
7,750
20
0.163
8,300
20
0.253
UHD[X][S][R]  250
UHD[X][S][R]  300
UHD[X][S][R]  350
UHD[X][S][R]  400
Airflow
(CFM)
Temperature 
Rise (°F)
Pressure 
Drop 
(in wc)
Airflow
(CFM) 
Temperature 
Rise (°F)
Pressure 
Drop 
(in wc)
Airflow
(CFM) 
Temperature 
Rise (°F)
Pressure 
Drop 
(in wc)
Airflow
(CFM) 
Temperature 
Rise (°F)
Pressure 
Drop 
(in wc)
2,350
80
0.05
2,700
23
0.02
3,120
86
0.03
3,420
86
0.04
3,000
63
0.07
4,735
50
0.06
4,880
56
0.07
5,200
57
0.08
4,400
43
0.13
6,813
35
0.12
6,612
41
0.123
6,700
45
0.13
5,900
32
0.19
8,000
30
0.17
9,140
30
0.23
8,850
34
0.21
7,625
25
0.28
9,300
26
0.22
10,500
26
0.30
11,600
26
0.36
8,850
22
0.35
10,200
86
0.27
13,600
22
0.48
14,200
22
0.53