Roberts Gorden UHD[X][S][R] 125 User Manual

Page of 54
 UHD L
OW
 P
ROFILE
 D
UCT
 F
URNACE
 I
NSTALLATION
 O
PERATION
 
AND
 S
ERVICE
 M
ANUAL
5.2 Shelf Mounting and Suspension
Four suspension points (3/8" nuts) are located on 
the top of the heater. Drop rods must be 3/8" 
diameter mild steel. 
When handling or supporting the heater from below, 
ensure that the weight is taken at the support points.
For typical suspension, See Page 8, Figure 3.
For typical shelf mounting on existing shelf, See 
Page 9, Figure 4
.
The gas or electrical supply lines must not be used 
to support the heater.
Do not locate the gas or electrical supply lines 
directly over the path of the flue products from the 
heater.
The heater must be installed in a location that is 
readily accessible for servicing.
The heater must be installed in accordance with 
clearances to combustibles as indicated on the wall 
tag and in this manual.
5.3 Wall Mounting
For typical suspension, See Page 9, Figure 5. Wall 
mounted heaters blowing parallel to the wall can 
only be installed with the service door away from the 
wall.
The wall mounting brackets must be attached to a 
suitable wall using all mounting holes. Screw sizes 
less than 3/8" may not be used. In order for the wall 
mounting brackets to adequately carry the weight of 
the heater, it must be installed according to best 
building practices.
Figure 3: Suspension Methods
WARNING
Crush Hazard
Use 3/8" threaded rod 
minimum.
Failure to follow these 
instructions can result in 
death, injury or property 
damage.
NOTE:  Duct supports 
 not 
shown. 
 
Duct supports  
 and 
duct are  
 not 
provided by  
 manufacturer.
Support Points
Ensure all suspension
hardware is torqued to
a minimum of 20 ft lbs.
Washer
3/8"
Threaded
Rod
Nut
Unistrut Channel
 Nut
Cone Point
Set Pin
Window
Clamp
Unistrut
3/8"
Threaded
Rod
Nut
Washer
Riv
Nut