Schneider Electric ACECFR20101SE User Manual

Page of 32
11
EcoBreeze System Installation
Service access
Install a service platform (not supplied) to facilitate maintenance activities. Regular 
maintenance activities require a of minimum 1219 mm (48 in.) clearance on all sides to 
remove, maneuver, and install Modules and components. 
N
OTE
: Consider local soil conditions, codes, and loading when determining appropriate 
support footings.
To prevent short cycling of outdoor air, each EcoBreeze Frame must have a minimum of 1219 
mm (48 in.) clearance on each side, totaling 2438 mm (96 in.) between Frames, and 1219 mm 
(48 in.) at the end of the Frame.
na3526a
1219 (48)
1219 (48)
1219 (48)
1219 (48)
1219 (48)
2438 (96)
1219 (48)
1219 (48)
na3677a
WALL OR OTHER OBSTRUCTION
* Dimensions are shown in millimeters with inches in parentheses.