EcoBreeze System Installation
Building Management System
The Modbus interface allows the EcoBreeze System to communicate with a building 
management system (BMS). 
The Modbus connection is available in two locations on the Modbus hub:
•  RJ-45 In port
•  3-wire on terminal block
For an RJ-45 connection, wire as follows: 
For a direct 3-wire connection, connect to the corresponding contacts on the green terminal 
block on the side of the Modbus hub. No connection is necessary to the 0V contact.
Pin 4
D(A)
Pin 5
D(B)
Pin 8
Ground
1MOD
1MOD
D(B)
D(A)
0 V
na3660a
WIRING CONTACTS 
FOR DIRECT 3-WIRE 
CONNECTION
RJ-45 IN PORT
DDC PANEL 
ENCLOSURE