Skuttle Indoor Air Quality Products 592-9 Leaflet

Page of 2
Skuttle
®
 Model 592-9 
24-Volt Spray Humidifier 
for Heat Pumps and  
High-Efficiency Furnaces 
IMPORTANT:  
THIS HUMIDIFIER MUST BE INSTALLED BY A QUALIFIED CONTRACTOR. 
DO NOT INSTALL ON ANY SYSTEM WITH WATER PRESSURE  
LESS THAN 40 P.S.I. 
Installation on water systems with hardness ratings greater than 7 grains 
is not recommended. Such installations can result in nozzle blockage, 
dripping, erratic spray patterns and other maintenance problems.       
Hardness above 7 grains will also produce dust from solids in the water 
supply, which will be distributed throughout the home. Consult your     
municipal water provider before continuing. 
SAFETY PRECAUTIONS 
READ THESE PRECAUTIONS AND ALL INSTALLATION INSTRUCTIONS 
BEFORE INSTALLING THE HUMIDIFIER.  
NOTE: Skuttle Mfg. Co. assumes no responsibility under warranty  
if installer does not follow these instructions and safety precautions. 
Do not install a humidifier where the heating temperatures can exceed 200°F. 
Excessive  temperatures  will  damage  the  humidifier,  possibly  causing  an 
overflow condition and water damage to the home.  
Do not install a humidifier where the surrounding temperature can be 32°F 
or  colder.  Frozen  water  will  damage  the  humidifier  and  burst  the  supply 
pipe, resulting in home damage.  
Do  not  cut  or  drill into  any  air  conditioning  or  electrical  accessories  during 
humidifier installation. DANGER:  Electrocution  is  possible  if  you  come 
in contact with a live wire; blindness can occur if refrigerant contacts 
your eyes. 
 
When  the  humidifier  is  installed  in  an  area  where  water  damage  could    
occur, connect the humidifier’s overflow provision to a suitable drain pan.  
For above-ceiling installations, always install a drain safety pan, plumbed to 
a suitable drain.  
For  initial  recommended  humidistat  settings,  refer  to  Table  1,  below.  (Be-
cause  relative  humidity  affects  people  differently,  these  settings  can  be 
raised or lowered slightly to suit personal comfort levels.) 
CAUTION:  Setting  the  humidistat  higher  than  the  recommended  set-
ting  can  cause  condensation,  resulting  in  home  damage.  
If excessive 
moisture  appears  on  windows  or  walls,  reduce  the  humidistat’s  humidity 
setting enough to eliminate condensation. If the situation continues, turn off 
the humidifier’s water source until condensation is gone.  
Make  sure  the  installation,  wiring  and  plumbing  of  the  humidifier  comply 
with local codes, ordinances and regulations.  
INSTRUCTIONS 
GENERAL INFORMATION:  
1.0  This humidifier puts moisture into the home by spraying a fine mist of water 
into the warm air plenum, which is carried into the living area by the duct system.  
1.1    When  wired  as  recommended,  the  humidifier  will  operate  only  when  the 
furnace blower is operating and the humidistat is calling for humidity.  
1.2  The nozzle capacity (flow) is rated at 40 P.S.I. This capacity varies accord-
ing to line pressure, as shown in Table 2, below. Select the nozzle that delivers 
the required spray in accordance with the pressure in your area. 
 
 
1.3  If the water pressure is excessive, a pressure regulator valve will be neces-
sary to obtain the proper volume of moisture.  
REQUIRED TOOLS:  
2.0  Aviation Snips  •  #2 Flathead Screwdriver  •  #1 Phillips Screwdriver  •  Ad-
justable Wrench  •  Pliers  •  Electric Drill with 7/64", 3/32", 1/4" and 3/8" Drill 
Bits  •  Hammer  •  Center Punch 
 
INSTALLATION INSTRUCTIONS 
Outside            
Temperature 
Recommended  
Setting 
Outside            
Temperature 
Recommended  
Setting 
-
20°F 
Low 
+10°F 
Med 
-
10°F 
Low 
+20°F 
High 
0°F 
Med 
Above +20°F 
High 
Table 1 
 
Capacities in G.P.H. at Various Water Pressures 
Nozzle Size  
40 P.S.I. 
60 P.S.I. 
80 P.S.I. 
100 P.S.I. 
125 P.S.I. 
.37 
.37 G.P.H. 
.45 G.P.H. 
.55 G.P.H. 
.60 G.P.H. 
.70 G.P.H. 
.50 
.50 G.P.H. 
.60 G.P.H. 
.70 G.P.H. 
.80 G.P.H. 
.85 G.P.H. 
.75 
.75 G.P.H. 
.89 G.P.H. 
1.10 G.P.H. 
1.20 G.P.H. 
1.40 G.P.H. 
1.00 
1.00 G.P.H. 
1.20 G.P.H. 
1.40 G.P.H. 
1.60 G.P.H. 
1.70 G.P.H. 
1.50 
1.50 G.P.H. 
1.80 G.P.H. 
2.10 G.P.H. 
2.40 G.P.H. 
2.70 G.P.H. 
2.00 
2.00 G.P.H. 
2.50 G.P.H. 
2.80 G.P.H. 
3.20 G.P.H. 
3.50 G.P.H. 
Table 2
 
 
 
 
 
 
 
 
 
101 Margaret Street, Marietta, OH 45750 
Phone: (800) 848-9786  •  Fax: (740) 373-9565 
Email: techservice@skuttle.com  •  Web: www.skuttle.com 
INSTALLING THE HUMIDIFIER:  
3.0   
CAUTION:  When  selecting  a  location  for  the  humidifier,  make  sure  the 
spray will not impinge or accumulate on any fan, limit controls, resistance heat-
ing coils or heating/air coils. 
 
3.1    Select  a  location  where  the  air  will  push  the  spray  mist  away  from  the      
humidifier.  
3.2  Mount the humidifier on the warm air 
plenum only, with the nozzle pointing up in 
the direction of airflow (see Figure 1, left). 
On  narrow plenums, mount the humidifier 
on the narrow side.  
3.3    If  there  is  not  enough  room  on  the 
warm  air  plenum,  mount  the  humidifier 
further  downstream  on  the  warm  air  duct, 
away from the heating and cooling coil.  
3.4    If  it  is  necessary  to  mount  the  spray 
nozzle further away from the humidifier (in 
order  to  move  the  nozzle  further  into  the 
air  stream  for  better  absorption),  remove 
the nozzle adapter and 45° fitting from the 
solenoid valve. Use the fittings supplied in 
the parts bag to relocate the nozzle using 
1/4"  copper  tubing  (not  supplied).  (See 
Figure  2,  below,  left.)    
CAUTION: Do not 
allow  copper  tubing  to  come  in  contact 
with  sharp  edges  or  surfaces  that  may 
cause wear on the tubing. 
 
3.5    Tape  the  template 
(provided)  on  the  warm  air 
plenum  in  the  location   
selected  for  the  humidifier. 
CAUTION:  Make  sure  the 
template is level. 
 
3.6  Center punch and drill 
four  7/64"  mounting  holes, 
as  shown  on  the  template. 
DANGER:  Make  sure  you 
are not cutting or drilling in-
to air conditioning or elec-  
                                                                                      trical accessories. 
 
3.7   Drill  a  3/8"  hole in  the 
center  of  the  shaded  area 
of  the  template;  cut  a  rec-
tangular  opening  (staying 
within the shaded area), as 
indicated.  
3.8    Install  the  drain  cup 
over  the  nozzle;  attach  it 
with  a  #6  x  3/8"  sheet 
metal  screw.  (See  Figure 
3, left.) 
3.9  Install 3/16" I.D. tubing 
on  the  copper  humidifier 
drain  and  run it  to  a  waste 
drain.  (An  occasional  drip 
from the drain tube when  
                                                                                      the humidifier is operating  
                                                                                      is normal.) 
                                                                                      3.10  Attach the humidifier  
                                                                                      with four #8 sheet metal  
                                                                                      screws.  
 
INSTALLING THE INSPECTION WINDOW:  
NOTE: A clear, plastic window is supplied with the humidifier to be mounted on 
the  ductwork.  This  allows  you  to  observe  whether  the  humidifier is functioning 
properly,  and  whether  there  is  water  impinging  on  parts  or  surfaces  within  the 
system.  
4.0    Select  a  mounting  location  on  the  ductwork  where  the  humidifier  spray  
nozzle can be viewed easily.  
4.1  Drill a 3/8" hole and cut a 4-1/2" x 2" rectangular opening. 
DANGER:  Make 
certain that you are not drilling or cutting into any air conditioning or elec-
trical accessories during installation. 
 
4.2    Position  the  window  over  the  opening;  mark  and  center-punch  the  two 
mounting hole locations.  
4.3  Drill the two 3/32" mounting holes.  
4.4  Attach the window with the two #6 Phillips-head screws provided.  
Part No. 000-0756-233 
Rev. 8/03 HBP 
  BEGIN READING ON OPPOSITE PANEL 
 
Continued on back... 
Figure 1
 
Figure 2
 
Figure 3
 
EXAMPLE:  A home which requires .50 gallons of water per hour for proper hu-
midification, and which has a water pressure of 80 P.S.I., would need a .37 noz-
zle to do the job.