Armstrong World Industries EHU-703 User Manual

Page of 40
PRE-INSTALLATION 
1)   CHECK SHIPMENT
A claim should be filed with the transportation company (and reported to Armstrong) if any items
are missing or damaged. Your shipment will arrive in two or three cartons.
One carton holds the humidifier with the steam generator installed, the control humidistat and
sensing element, two short steam hoses, hose clamps, mounting plate and lag screws, and a 
clear drain hose. If you have ordered a duct pressure switch or a high limit stat, these too will
be in the humidifier carton.
The steam dispersion tube(s) and fittings are contained in another carton ( two for the EHU 704).
Two complete sets of                          
installation instructions have
been shipped with your unit. 
One is for the installer's use. 
The second is for the owner's
files.
2)   CHECK LOCAL CODES
Series EHU-700 humidifiers 
should be installed in 
accordance with ALL
applicable building, plumbing,
and electrical codes.
3)   SITE SELECTION  
Electronic steam humidifiers 
must be installed in locations 
that allow routine inspection 
and accessibility for maintenance 
operations.  See Figures 4-1 & 4-2 
for access space.
Do not place electronic steam humidifers 
in locations where unusual instances of 
malfunction of the humidifier or the 
system might cause damage to 
non-repairable or un-replaceable, 
or priceless property.
4
4" Side
Clearance
Both Sides
5" Min. Drain
Connection Access
24" Min. Steam 
Generator
Tank Removal
4" Side
Clearance
24" Front
Clearance
5" Min. Drain
Connection Access
24" Side
Clearance
Figure 4-2. EHU-703/704
Figure 4-1. EHU-701