D9412GV3/D7412GV3 | Operation and Installation Guide | 4.0 
Installation 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
14
 
3.3.13  Ground Fault Detection Added Feature 
When Ground Fault Detect is enabled (S4 closed), 
Points 1 to 8 can be used for non-powered fire-
initiating devices such as heat detectors, four-wire 
smoke detectors, and pull stations. A D125B Powered 
Loop Interface or a D129 Dual Class A Interface 
Module is not required when connecting the non-
powered fire-initiating devices to Points 1 to 8. 
3.3.14 Conettix Functions 
The D6600 Conettix System supports data network 
communications. Conettix allows the D6600 Receiver 
to connect to various network technologies including 
Ethernet and GPRS (General Packet Radio System). 
Connecting to a data network is possible using the 
COM4 or COM1 connection from the D6600 Receiver 
to the D6680 Network Adapter. Control panels can 
send reports through telephone lines, Ethernet, 
Token-Ring or GPRS networks to the D6600 receiver 
at the central station. Once events are received, they 
can then be issued to automation software or a 
network printer through a local area network (LAN) or 
wide area network (WAN). 
Sending events to the central station over a LAN or 
WAN requires a network interface module (NIM), such 
as the DX4020. Sending events over GPRS requires 
a special NIM, the ITS-DX4020-G. 
3.3.15 Programming 
Use the Remote Programming Software (RPS), or the 
local Programmers Menu, to program the D9412GV3 
and D7412GV3 Control Panels. Refer to the 
D9412GV3/D7412GV3 Program Entry Guide (P/N: 
F01U170807) for programming options. 
3.3.16 Other Features 
D9412GV3 and D7412GV3 Control Panels have 
many programmable features. Some of the features 
are listed below. Complete details on all features are 
in the D9412GV3/D7412GV3 Program Entry Guide  
(P/N: F01U170807). 
  Supervision of AC (primary power), battery 
(secondary power), Zonex and SDI buses, central 
processing unit (CPU), up to three printers, and 
two telephone lines 
  Automatic System Test Reports 
  Remote access for programming, diagnostics, 
and log uploads using the remote programming 
software (RPS) 
  Fire alarm verification 
  Programmable alarm output 
  Programmable relay output using the D8129 
OctoRelay Module 
  Opening and closing windows 
  Skeds (scheduled events) 
  Limited local programming available in the 
Service Menu 
4.0 Installation 
4.1 Installation 
Preparation 
This section contains a general installation procedure 
and refers to other sections of the document for 
detailed instructions.  
Review this document and the D9412GV3/D7412GV3 
Program Entry Guide
 (P/N: F01U170807) before 
beginning the installation to determine the hardware 
and wiring requirements for the features used. 
Have the following documentation available when 
reading through this guide: 
  D9412GV3/D7412GV3 Program Record Sheet  
(P/N: F01U170809) 
  Security System Owner’s Manual  
(P/N: 71-06633-000) and GV3 Series Owner’s 
Manual Supplement
 (P/N: F01U143082) 
  Installation manual for keypad or annunciator 
(D1255 all models, D1255RB, D1256, D1256RB, 
D1257, D1257RB, D1260 all models, or D720 all 
models) 
Before installation, become familiar with the operation 
of RPS or the local Programmers menu. 
4.2 Enclosure 
Options 
Mount the control panel assembly in any of the Bosch 
Security Systems, Inc. enclosures listed: 
  D8103 Universal Enclosure (tan) 
  D8109 Fire Enclosure (red) 
  D8108A Attack Resistant Enclosure (tan) 
Refer to the D9412GV3/D7412GV3 Approved 
Applications Compliance Guide
 (P/N: F01U143069) to 
determine if the application requires a specific 
enclosure. 
4.3 Mounting 
Enclosure 
1.  Run the necessary wiring throughout the 
premises.  
2.  Mount the enclosure in the desired location. Use 
all five enclosure mounting holes. Refer to 
Figure 2
3.  Pull the wires into the enclosure. 
 
Electromagnetic interference (EMI) can 
cause problems on long wire runs.