Bosch d9412gv3 User Manual

Page of 76
D9412GV3/D7412GV3 | Operation and Installation Guide | 4.0 
Installation 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
18
 
4.8 Installing 
the 
Point Chart Label 
 
The point chart label is required for fire 
systems with verifications points. 
A point chart label is included in the literature pack. 
Install the point chart label for fire or combined fire-
and-burglary systems that use verification points. 
Use the D9412GV3/D7412GV3 Program Record 
Sheet
 (P/N: F01U170809) to gather the necessary 
information for completing the point chart. Fill out the 
label and install it on the inside of the enclosure door 
(refer to Figure 2 on page 15). 
 
Avoid smearing the entries on the chart. 
Use the peel-off backing to press the 
label in place. 
4.9 
Testing the System 
After installing and programming the control panel, 
test the system completely. Test the control panel and 
all devices for proper operation.  
 
Test after initially programming the control 
panel. 
To meet UL 864 requirements, perform a 
full system test after any subsequent 
programming session. 
Refer to Section 4.10 Service Walk Test on page 18 
for complete Service Walk Test instructions. 
Clear after Test: To clear the event memory and 
report buffer, momentarily close the reset pin. Events 
stored in the control panel’s event log are not cleared. 
4.10  Service Walk Test 
The Service Walk Test differs from the standard Walk 
Test. In the standard Walk Test, POPITs whose 
switches are set for a point number not programmed 
in the control panel do not appear in the test. In the 
Service Walk Test, POPITs whose switches are set 
for a point number that is not programmed in the 
control panel do appear in the test.  
The Service Walk Test allows a user to walk test all 
246 points from a control-panel-wide keypad, 
regardless of the point index type.  
A Service Walk Test can also be initiated by account-
wide or area-wide keypads but test only those points 
that are within the scope of the keypad that initiated 
the function. The Service Walk Test does not test 
points in armed areas. 
 
Only Walk Test Start and Walk Test End 
are reported to the central station. 
 
 
The D9131A can be configured for local 
printing. Refer to the D9412GV3/ 
D7412GV3 Program Entry Guide
 
(P/N: F01U170807). 
 
 
During a Service Walk Test, the summary 
alarm and summary fire remain off, 
because there are no Fire or Burg alarm 
conditions to summarize. The P# Relay 
Response Type feature operates as 
programmed. 
 
Service Walk Test Procedure.  
Refer to Figure 5 on page 20 and Figure 6 on page 21 
for Service Walk Test options. Refer to the Walk Test 
procedures in the GV3 Series Owner’s Manual 
Supplement
 (P/N: F01U143082) when using a D1260 
or D1260B Keypad. 
1.  Choose a keypad to conduct the test. Ensure that 
the display shows the idle disarmed text. 
2.  Press the [MENU] key to enter the Function List. 
Press [NEXT] repeatedly until the SERVICE  
WALK ? prompt appears.  
3.  Press [ENT], or press [9][9] followed by [ENT] to 
reach the Service Menu to access the Service 
Walk Test. 
 
The D7412GV3 does not include the 
Service Walk Test in the Service Menu. 
Enabling the Service Walk Test function 
in the Function List provides access to 
the Service Walk Test in the D9412GV3.  
4.  The display shows ### PTS TO TEST .Test the 
first detection device. 
5.  When a detection device is faulted, the keypad 
emits a brief tone and displays the point text of 
the point tested for 60 sec. After 60 sec, the 
display returns to the ### PTS TO TEST 
message. 
Extra Points display default text:  If the switches on 
a POPIT are set  incorrectly to a point number that is 
not in the program for the control panel, the default 
text for that point number (PT ###) appears when the 
point is faulted. Refer to the control panel’s program 
record sheet for the default text for all points.   
Faulting the point a second time produces the tone 
and shows the point text, but does not decrease the 
count in the ## PTS TO TEST message.