Power Outputs 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
26
 
6.0 Power 
Outputs 
6.1 Circuit 
Protection 
Three self-resetting circuit breakers protect the control 
panel from short circuits on the continuous and 
programmable power outputs. If the control panel is 
programmed for power supervision and a short circuit 
occurs on one of the power outputs, the control panel 
sends BATTERY LOW and BATTERY MISSING 
when using Bosch Security Systems, Inc. Modem IIIa
2
 
communicator format. Under the same conditions 
when using Contact ID communicator format, the 
control panel sends Control Panel Battery Low (302) 
and Control Panel Battery Missing (311). 
One self-resetting circuit breaker protects: 
  Terminal 3: Auxiliary Power 
  Terminal 24: Zonex Power  
 
 
A short circuit on one terminal disrupts 
power to the other terminal. 
Another self-resetting circuit breaker protects: 
  Terminal 6: Alarm Power Output 
  Terminal 7: Alternate Alarm Power Output 
  Terminal 8: Switched Auxiliary Power. 
 
A short circuit on one of the terminals 
disrupts power to the other two terminals. 
The third self-resetting circuit breaker protects 
Terminal 32: Power +. 
 
UL requires any device powered from a 
power output to be supervised. 
 
 
UL requires that power outputs are not 
shared between fire and non-fire devices 
unless all devices are in conduit within 
20 ft and are in the same room. 
 
6.2 
Total Available Power 
The system produces up to 1.4 A of combined power 
at 12.0 VDC nominal for special application use. The 
outputs listed below share the available power. These 
outputs are shown as red circles on the faceplate.  
Terminal 3 - Auxiliary Power: Use this terminal to 
power devices requiring continuous power. 
Terminal 6 (Relay A) - Alarm Power Output: 
Programmable relay normally open, power on alarm. 
Terminal 7 (Relay B) - Alternate Alarm Power 
Output:
 Programmable relay normally open, power 
on alarm. 
Terminal 8 (Relay C) - Switched Auxiliary Power: 
Programmable relay normally closed, switches power 
off when the Sensor Reset command is executed. 
Terminal 24 - Zonex Power: Use this terminal to 
power Zonex modules such as the D8125, D8128D, 
and D8129 Modules.  
Terminal 32 – SDI Power +: Use this terminal to 
power serial device interface (SDI) devices such as 
keypads, the D9131A Parallel Printer Interface 
Module, and the D9210B Wiegand Control Interface 
Module.  
Accessory Connector: The D928 Dual Phone Line 
Switcher connects to the accessory connector. 
6.3 Continuous 
Power Output 
Terminals 3, 8, 24, and 32 
The continuous current draw for powered devices 
connected to Terminals 3, 8, 24, and 32, and the 
accessory connector must not exceed 1.4 A. Devices 
powered from these outputs operate at 12.0 VDC 
Nominal. 
Power Restricted for Fire and Combined Fire and 
Burglary Systems:
 Use the Fire System Power 
Formula to calculate the current available for fire and 
combined fire and burglary systems (refer to Section 
6.4 Programmable Power Output Terminals 6, 7, and 
8).