9.0   Off-Board Points 
9.1 
Point (Zonex) Bus: D9412GV3 
Terminals and D7412GV3 
Terminals  
9.1.1 POPIT 
Modules 
The D9412GV3 can use point of protection input 
transponder (POPIT) modules to provide a maximum 
of 238 off-board points, bringing the total number of 
points the D9412GV3 can monitor to 246. The 
D7412GV3 provides up to 67 off-board points, 
bringing the total number of points the D7412GV3 
monitors to 75. Each off-board point requires a POPIT 
Module.  
The expansion bus can be shared 
between fire and non-fire devices where 
the POPIT module provides data isolation 
between the input and the bus 
connections. 
9.1.2 POPEX 
Modules 
POPITs connect to supervised two-wire data 
expansion loops run from POPIT to POPIT throughout 
the premises. Data expansion loops connect to a 
D8125 Point of Protection Expander (POPEX) 
Module. POPEX Modules have power and data 
connections to the point bus on the control panel 
(Table 10). 
Table 10:  POPEX Modules 
 
Model Power 
Data 
D9412G 
Terminals 23 and 24 
Terminals 25 and 26    
or 
Terminals 27 and 28 
D7412G 
Terminals 23 and 24 
Terminals 27 and 28 
9.1.3 Missing 
Conditions 
If a programmed POPIT is disconnected from the 
expansion loop, a missing condition appears 
immediately and the event is logged. The missing 
condition might also be sent to a central station or 
printed to an on-site printer, if programmed to do so. 
Refer to the D9412GV3/D7412GV3 Program Entry 
Guide
 (P/N: F01U170807) for programming options.  
9.1.4 Extra 
Point 
Events 
Extra Point events are generated when a POPIT 
connected to the data expansion bus does not have 
an assigned Point Index. Table 11 shows when an 
Extra Point event is or is not generated. Table 12 on 
page 37 shows additional error conditions that can 
occur for the off-board points.
 
Table 11:  Extra Point Events 
 
A POPIT connected to the data 
expansion bus does not have an 
assigned Point Index and: 
Extra Point event?  Additional Information 
Data expansion bus is disconnected 
No 
Keypad does not annunciate or display a trouble 
condition. 
Data expansion bus restores to 
normal condition after an open 
condition 
Yes 
 
Keypad annunciates and displays a trouble 
condition 
 
Extra Point is logged and might be programmed to 
send reports to the central station or to an on-site 
printer. 
Point input changes status from 
normal to open or shorted 
No 
Keypad does not annunciate or display a trouble 
condition. 
During a Service Walk Test, the point 
input changes status from normal to 
open or shorted 
Yes
 
 
Keypad annunciates and displays a trouble 
condition 
 
Extra Point is logged and might be programmed to 
send reports to the central station or to an on-site 
printer. 
 
 
The Service Walk Test never shows the electrical state of a point as “Extra.”