Off-Board Points 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
37
 
Table 12:  Off-Board Point Errors 
 
Error Condition 
Result 
Additional Information 
+/- leg of the data expansion bus has a 
short circuit to earth ground, with 
Ground Fault Detect enabled 
Ground Fault event 
 
+/- leg of the data expansion bus is 
disconnected 
All POPITs beyond the 
disconnection send Missing 
report 
 
Data expansion bus has a short circuit 
 
All POPITs send Missing 
report 
 
Pt Bus Trouble event 
When the data expansion bus restores, Pt 
Bus Restore event occurs. If any POPIT is 
connected to the data expansion bus 
without an assigned Point Index, an Extra 
Point event occurs.  
+/- leg of the data expansion bus has a 
short circuit to the Common terminal on 
the control panel 
 
All POPITs send Missing 
report 
 
Pt Bus Trouble event 
 
Terminal 26, 28, or 94 has a short 
circuit to a Common terminal 
No Pt Bus Trouble event occurs   
Terminal 25, 27, or 94 has a short 
circuit to a Common terminal 
 
Pt Bus Trouble event 
 
Keypad displays: 
SERVC ZONEX 1 
 
Terminals 27 and 28 have a short 
circuit together 
 
Pt Bus Trouble event 
 
Keypad displays: 
SERVC ZONEX 1 
 
9.1.5  D9412GV3/D7412GV3 Responses to 
Missing Point Conditions  
The D9412GV3 and D7412GV3 respond to missing 
point conditions based on the point’s programming 
and the armed state of the point’s area. For example, 
if an interior motion detector point is missing during a 
disarmed state, a Missing Trouble event is generated; 
however, if the point is missing while the area is 
Master Armed, a Missing Alarm event is generated. 
Non-fire, 24-hour points always generate a Missing 
Alarm event, whereas Fire points always generate a 
Missing Fire Trouble event. 
9.2 
D8125 and D9127 POPIT Modules 
D9127 POPITs use the D8125 POPEX Module to 
report to the control panel. Each D8125 supports up 
to 119 POPIT points. Connect two D8125 Modules to 
the D9412GV3 to bring the combined total number of 
POPIT and on-board points to 246.  
  Points 9 to 127 connect to the first POPEX 
Module.  
  Points 129 to 247 connect to the second POPEX 
Module.  
  The D9412GV3 reserves Points 128 and 248 for 
internal use.  
The control panel annunciates activity only for each 
POPIT, not for each detection device connected to 
the sensor loop.  
The D9127 Module enclosures are made of UL Listed 
fire resistant material. D9127T Modules contain 
tamper switches. D9127U Modules include 
untampered covers. Unless the module is mounted in 
a tampered enclosure, UL requires D9127T Modules 
for certificated accounts. 
Listings 
The D8125 POPEX and the D9127 POPIT Modules 
are UL Listed for Local or Police Connected Burglar 
Alarm, Central Station Burglar Alarm, Household 
Burglar Alarm, Central Station Fire, Local Fire, 
Remote Station Fire, Household Fire, and Electrically 
Actuated Transmitter Applications. 
Refer to the D9412GV3/D7412GV3 Approved 
Applications Compliance Guide
 (P/N: F01U143069) to 
determine the required equipment and enclosures for 
the application.