D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0  
Off-Board Points 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
45
 
Use the point DIP switches to disable conflicting 
points, such as when a D9210B Access Control 
Module must be assigned to a point that falls within 
the range of the D8128D OctoPOPIT. In this example, 
a D9210B is assigned to Point 20. On the same 
system, a D8128D OctoPOPIT is assigned to Points 
17 through 24. Moving the DIP switch for Point 4 to 
the OFF position would effectively disable Point 20, 
allowing normal operation of the D9210B and the 
OctoPOPIT. 
Terminate each OctoPOPIT sensor loop with a 1 kΩ 
EOL resistor. Attach a resistor even if you do not 
enable the loop. 
9.4.5 Mounting 
OctoPOPITs 
The D8128D OctoPOPIT Module can be installed in 
the enclosure with the control panel using standard 
four-conductor 0.8 mm (22 AWG) wire, or in a 
separate enclosure (Model D8103, D8103A, or 
D8109) up to 61 m (200 ft.) from the control panel 
using shielded (recommended) standard four-
conductor 0.8 mm (22 AWG) wire. If using the D125B 
or D129, refer to the Specifications section of the 
D8128D Installation Guide (P/N: F01U070537) for 
cabling requirements. 
For UL Listed systems, mount the D8128D in a 
tamper-proof enclosure. To install OctoPOPITs in the 
control panel’s enclosure, complete the following 
procedure. Use the D137 Mounting Bracket to install 
OctoPOPITs in enclosures with no module-mounting 
locations available. 
1.  Align the OctoPOPIT module using any of the 
four mounting locations in the enclosure. Refer to  
Figure 2 on page 15. 
2.  Use the screws provided with the module to 
secure it in the enclosure. 
9.4.6 Wiring 
OctoPOPITs 
 
Warning: Disconnect all power to the 
control panel before beginning any work 
with the internal components. Serious 
injury could result from electrical shock. 
1.  Power down the control panel: 
a.  Disconnect the positive (red) battery lead at 
the battery. 
b.  Unplug the transformer. 
 
 
A D8128D OctoPOPIT can be installed 
up to 61 m (200 ft.) from the control 
panel. 
 
2.  Connect the D8128D to the control panel using 
either of the following methods: 
  Wire the D8128D to the terminal strip on the 
side of the POPEX Module, or  
  Connect the D8128D using the Molex
®
 
connectors (P1 and P2). Refer to Using 
Molex® Connectors
 on page 48. 
 
 
Caution - AC induction: Avoid installing 
Zonex data wires and Zonex input (sensor 
loop) wires around any AC conduit, wiring, 
or electrical devices that emit fields of 
electromagnetic interference (EMI). 
Using the Terminal Strip 
Refer to Table 16Figure 20 on page 46, and 
Figure 21 on page 47 when using the terminal strip to 
connect the D8128D OctoPOPIT to the control panel. 
Table 16:  Terminal Strip Connections 
D8128D 
D9412GV3 
D7412GV3 
Common 
Terminal 23 
Terminal 23 
Out 
Zonex 1 = Terminal 27 
Zonex 2 = Terminal 25 
Terminal 27 
In 
Zonex 1 = Terminal 28 
Zonex 2 = Terminal 26 
Terminal 28 
+12 V 
Terminal 24 
Terminal 24