D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0  
Off-Board Points 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
46
 
 
Figure 20:  Connecting D8128D OctoPOPITs to the D9412GV3 
 
1 -  Zonex Bus 1, Switch 1 ON (Points 9 to 72) 
2 -  Bus 1 
3 -  First address on Zonex Bus 1 
4 -  Last address on Zonex Bus 1 
5 -  Zonex Bus 1, Switch 1 OFF (Points 73 to 127) 
6 -  Sensor loops 
 
7 -  Zonex Bus 2, Switch 1 ON (Points 129 to 
192) 
8 -  Bus 2 
9 -  First address on Zonex Bus 2 
10 -  Last address on Zonex Bus 2 
11 -  Zonex Bus 2, Switch 1 OFF (Points 193 to 
240) 
 
 
Refer to Address Switches in Section 9.4.4 Setting the OctoPOPIT Switches on page 44 for 
information about making these switch settings. Refer to Table 15 on page 44 for information 
about setting Switch 5. 
 
 
 
For system supervision, do not use looped wire terminals. Break the wire run to provide 
supervision of the connections.