D9412GV3/D7412GV3 | Operation and Installation Guide | 13.0 Programmer and Accessory Connections 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
62
 
13.0 Programmer and 
Accessory Connections 
13.1 Programmer 
Connector 
Control panel firmware version 8.11 and later does 
not support the D5200 Programmer. Instead, a limited 
local keypad programming mode is available. Refer to 
Section 13.2 Installer Keypad and Local Programmers 
Mode
 on page 62 for details.  
 
Figure 31:  Reset Pin 
1 -  Reset Pin locked (closed) 
2 -  Reset Pin normal (open) for normal control 
panel operation 
 
 
When the Reset Switch (labeled S1) 
is closed, the communication module 
at SDI Address 92 is disabled. While 
in this mode, remote programming 
communication is only supported by 
the communication module at SDI 
Address 88. 
13.2  Installer Keypad and Local 
Programmers Mode 
While installing or maintaining a D9412GV3 or 
D7412GV3 control panel, it is sometimes necessary 
to change the configuration. To do so, a local keypad 
programming menu is available in the Service Menu. 
You can access the Service Menu when the control 
panel is in stand-by mode or while it is operating. 
Refer to the D9412GV3/D7412GV3 Control Panel 
Program Entry Guide
 (P/N: F01U170807) for an 
explanation of the programming menu. 
Accessing Local Keypad Programming when the 
Control Panel is Operating (Reset Switch Open) 
To access the Local Programmers Menu while the 
control panel is operating: 
1.  Disarm all areas in the control panel. 
Local keypad programming is only accessible 
when all areas are disarmed. 
2.  At any D1255 or D1260 Keypad, press 
[9][9][ENTER] to access the Service Menu. 
3.  Enter the Service passcode when prompted. 
4.  Advance the menu to the Keypad Programming 
option, then press [ENTER] to enter programming 
mode. 
The Keypad Programming menu is only available 
when all areas in the control panel are disarmed.  
Accessing Local Keypad Programming when the 
Control Panel is in Standby Mode (Reset Switch 
Closed) 
The control panel is in standby mode when the Reset 
pin is closed. Refer to Figure 31. While the control 
panel is in standby mode, you can access the Service 
Menu at one of two keypads with the following 
restrictions: 
  An unsupervised D1260 Keypad (all versions) 
at SDI Bus Address 8. 
The D1260 Keypad does not support SDI Bus 
Address 16. 
  An unsupervised D1255 Keypad (all versions) 
at SDI Bus Address 16. 
If a D1255 is set to SDI Bus Address 8, then 
that keypad cannot be used to access the 
Service Menu. 
  Only one keypad at a time is allowed to be in 
use. 
To access Local Keypad Programming when the 
control panel is in standby mode: 
1.  From the keypad (D1260 at SDI Address 8 or 
D1255 ad SDI Address 16), enter the Service 
Passcode. 
2.  Advance the menu to the Keypad Programming 
option. 
3.  Press [ENTER] to enter Local Keypad 
Programming. 
13.3 Programmer 
Access 
Reports 
When a program is sent to the control panel from 
RPS, the control panel sends a Prog Access OK 
report 10 sec after the reset switch is unlocked, or 
when the programmer disconnects. The prompt in 
routing must be programmed Yes to send this report.