Panasonic WJ-HD309 User Manual

Page of 164
@5
Pin No.
82
■ How to Use the Terminals of the ALARM/CONTROL Connector
These terminals are used for emergency recording, auto time adjustment (Auto Adjust Time), taking measures against power
outages (Shutdown Time), and when installing a buzzer, a lamp, or similar alarm device. They are also used to synchronize
with the sequential display changeover.
The terminal pin array and connections are shown below. The con-
nector used should be compatible with the pin configuration.
Pin array
The pin array is different from other disk recorders. Make sure that
the connection is correct referring to the following.
q
Pin No.
Ch 8 alarm output
Operation
Alarm signal output at an event occurrence
Open collector output 
24 V max., 100 mA
Starting emergency recording disk space a sig-
nal input
Generation of signal output for disk space alarm-
ing of DVD-RAM, DVD-R, CD-R
Open collector output 
24 V max., 100 mA
Remarks
w
Ch 9 alarm output
e
Ch 10 alarm output
r
Ch 11 alarm output
t
Ch 12 alarm output
y
Ch 13 alarm output
u
Ch 14 alarm output
i
Ch 15 alarm output
o
Ch 16 alarm output
!0
NC
!1
Alarm display reset input
!2
Emergency recording
input
!3, !4
Earth (Grounding)
!5
Alarm output for available
disk space of device con-
nected to copy port 
Signal output upon detection of HDD error
!6
HDD error output
Signal output upon detection of camera error
!7
Camera error output
Signal output upon detection of unit error
!8
Error output
Signal output upon completion of outage pro-
cessing
High (+12 V)
!9
End of outage process-
ing
Time of this unit is adjusted to the preset time
according to the signal input. This signal output is
then generated for the setting time of this unit.
Time of all other units is adjusted to the setting
time of this unit.
30 k
Ω 5 V pull-up,
–100 mA/make contact
@0
Time adjustment I/O
Sequence changeover is effected according to
the signal input. Signal output is generated at the
time of sequence changeover.
@1
Sequence changeover
I/O
The state of alarm suspension is assumed
according to the signal input.
@2
Alarm suspension input
Start of outage processing according to the sig-
nal input.
Non-voltage make contact input
–100 mA/5 V pull-up
@3
Outage detection I/O
Changeover to the external recording mode
@4
External recording mode
changeover
Canceling the alarm display
Non-voltage make contact input
–100 mA, 5 V pull-up
+5 V output
+5 V output
200 mA max.
q
!3
@5
!4
ALARM/CONTOROL