GENERAL INFORMATION
sEctioN 1.2
iNstallatioN Basics
poWer Source and load lineS
The  utility  power  supply  lines,  the  standby  (genera-
tor)  supply  lines,  and  electrical  load  lines  must  all  be 
connected  to  the  proper  terminal  lugs  in  the  transfer 
switch. The following rules apply: In 1-phase systems 
with  a  2-pole  transfer  switch,  connect  the  two  utility 
source  hot  lines  to Transfer  Switch Terminal  Lugs  N1 
and  N2.  Connect  the  standby  source  hot  lines  (E1, 
E2)  to  Transfer  Switch  Terminal  Lugs  E1  and  E2. 
Connect  the  load  lines  from Transfer  Switch Terminal 
Lugs T1 and T2 to the electrical load circuit. Connect 
UTILITY,  STANDBY  and  LOAD  neutral  lines  to  the 
neutral block in the transfer switch.
SyStem control interconnectionS
Home standby generators are equipped with a termi-
nal  board  identified  with  the  following  terminals:  (a) 
UTILITY  1,  (b)  UTILITY  2,  (c)  23,  and  (d)  15B.  Load 
centers  house  an  identically  marked  terminal  board. 
When these four terminals are properly interconnect-
ed,  dropout  of  utility  source  voltage  below  a  preset 
value  will  result  in  automatic  generator  startup  and 
transfer  of  electrical  loads  to  the  “Standby”  source. 
On restoration of utility source voltage above a preset 
value  will  result  in  retransfer  back  to  that  source  and 
generator shutdown.
Part 1
Page 13
0000001
GAS MAIN
2-5 PSI
5-7” WC REGULATOR
TO HOUSEHOLD
GAS METER CAPABLE
+HOUSEHOLD APPLIANCES
FUEL FLOW OF:
OF PROVIDING NATURAL GAS 
SAFETY
SHUT OFF
VALVE
(BASED ON 1000 BTU/CU FT)
BTU/HOUR
140,000 (7 kW)
156,000 (9 kW)
215,000 (12 kW)
220,000 (13 kW)
261,000 (16 kW)
294,000 (18 kW)
Figure 2. Proper Fuel Installation