total from the subtraction and subtract the next largest number possible and so on until 
the result is zero. Each value that was used in the subtraction indicates that the 
Transmitter is online. 
For example: The On/Offline Status holding register contains the value 15. In this case 
the largest value we can subtract is 8, which leaves a result of 7. Now we can subtract 4 
from 7 and get 3. Now subtract 2 from 3 and we get 1. Finally we subtract 1 from 1 and 
get 0, so we are done. Which Transmitters are online? We subtracted 8,4,2 and 1, and 
these numbers correspond to Transmitters’ with RF IDs 1,2,3 and 4. 
Note An alternate method to determining which Transmitter(s) are online is to look at the 
Base Radio Holding Register as a binary number with the rightmost bit representing 
Transmitter 1 and the leftmost bit representing Transmitter 16.  For example, the binary 
representation for Transmitters 1-4 online is as follows: 
0000000000001111   
In another example, say the On/Offline Status holding register contains the value 6. We 
can subtract 4 to get 2. Then we can subtract 2 to get 0. Thus Transmitter 2 and 3 are 
online, but Transmitters 1 and 4 are offline. 
6.5  Transmitter Holding Registers 
The following are the Transmitter holding registers when used in the Device ID Mapping 
Mode 
(First Table) and the Register Mapping Mode (Second Table). 
6.5.1  Device ID Mapping Mode 
Transmitter Holding 
Registers 
(DEVMODE Only)
 
Device ID 
Base Radio Modbus ID + RF ID 
 
Register Address 
Description 
Register Type 
00001 Device 
Type 
00002 Device 
Type 
32-Bit IEEE 
Floating Point 
00003 Device 
Status 
00004 Device 
Status 
32-Bit IEEE 
Floating Point 
00005 
Primary Sensor Value 
00006 
Primary Sensor Value 
32-Bit IEEE 
Floating Point 
00007 
Secondary Sensor Value 
00008 
Secondary Sensor Value 
32-Bit IEEE 
Floating Point 
00009 
Tertiary Sensor Value 
00010 
Tertiary Sensor Value 
32-Bit IEEE 
Floating Point 
 
6.5.2  Register Mapping Mode 
Transmitter Holding 
Registers 
(REGMODE Only)
 
Device ID 
Base Radio Modbus ID 
 
Register Address 
Description 
Register Type 
00001 + (RF ID * 10) 
Device Type 
00002 + (RF ID * 10) 
Device Type 
32-Bit IEEE 
Floating Point 
00003 + (RF ID * 10) 
Device Status 
00004 + (RF ID * 10) 
Device Status 
32-Bit IEEE 
Floating Point 
 
31