Omega CN154 User Manual

Page of 20
- 8 -
4-6. Supplementary explanation of screens 
(1) 0-1 Control Output Screen
• During manual control an output value is set on this
screen.  In automatic control, it is only for monitoring.
• For switching automatic control to manual, press the
key on the control output screen. 
• The MAN monitor LED flashes during manual control and
goes out when control is changed to auto.
• This screen is only for monitoring in the stop mode, when
AT is ON, or keylock is set at 2 or 3.
• Manual control output is released if the stop mode is
selected or the type of input or the measuring range is
changed during manual control.
• For changing the manual output value, the        and
keys are used.  It is not necessary to press the        key.
• During manual control, the setting range of control output
is between 0 and 100%.  In case an output limiter has been
set, that value serves as the higher/lower limit of the
setting range. 
• In ON/OFF action (P=0), manual control output should be
at 0% or 100% (For V and I output, lower limit output
limiter or higher limit output limiter). 
• When auto is changed to manual, the action becomes
balanceless and bumpless.  If the measured value (PV) is
out of the proportional band, it does not attain balanceless
and bumpless action. 
• If power is turned off during manual control output and is
turned on again, the condition is stored in the memory.
(2) 0-2  Control Execution/Stop Screen 
• Use the        and        keys to select control execution
(EXEC) or stop (STBY).  Then register it by means of the
key. 
• Upon selecting stop, the STBY monitor LED turns on and
the control output display turns to 0%. 
• Upon selecting execution, the mode changes to automatic
control; it is not possible to go directly from the stop to the
manual mode. When control is being executed, the STBY
monitor LED remains unlit.
• Even at stop, the alarm works.
• When AT is ON or 1, 2 or 3 of keylock has been selected,
no change is allowed. 
(3) 1-6  Manual Reset Value Setting Screen 
• In the PID operation, an offset is corrected automatically
by I, i.e., integral calculation.  When I is set at OFF, this
correction is not made and output is manually increased or
decreased for correction. This is called manual reset (MR). 
(4) 1-11  Proportional Cycle Setting Screen
• In the case of contact output or SSR drive voltage output,
time in which output is ON + time in which it is OFF in
the proportional band, that is, proportional cycle time is
set. 
(5) 1-12, 1-13  Lower Limit and Higher Limit Output Limiters 
Setting Screens
• The output limiters function effectively to maintain the
lowest  temperature, to suppress control overshoot by
limiting control output to minimum and maximum values
set. 
• In the output limiters, priority is given to the lower limit
value. Therefore, when the lower limit is set at a value
higher than the higher limit value, the higher limit value is
forced to be the lower limit value + 1%.  Therefore, the
higher limit value cannot be set to be less than the lower
limit value + 1%. 
ENT
Note:
Moving to another screen while maintaining the manual
mode is possible.  In this case, it should be noted that
control output is made manually.  The apparatus is in the
manual mode when the MAN monitor LED is flashing.
ENT
(6) 1-14  Soft Start Time Setting Screen 
• Soft start is the function selected to raise control output
gradually in the beginning of control.  It is effective in
preventing excessive current from flowing into a heater or
similar apparatus.
• Soft start functions in the following cases:
Upon applying power in the auto mode
When control stop (STBY) is changed to control 
execution (EXEC)
When scale-over is restored to the normal state (in auto
mode) 
The above are on condition that soft start time and
proportional band are not set at OFF.
• In the following cases, the soft start function is released.
Soft start time has elapsed without problem.
Auto is changed to stop or manual mode during the
execution of soft start.
Soft start time or proportional band is changed to OFF
during the execution of soft start.
The measurement range code is changed during the
execution of soft start. 
Control output characteristic is changed during the
execution of soft start. 
Scale-over of a measured value occurs during the
execution of soft start.
Control output falls to a level below the output value of
soft start during the execution of soft start.
• Auto tuning is unable to be carried out during the
execution of soft start.
5.  Operation
5-1. Setting of set value (SV)
(1) Press the        or        key to set set value.  Keep pressing it to
flash the point of the least digit of set value and increase (or
decrease) value.
(2) After confirming the value to coincide the set value, press
to register the data.
(3) After registration of the data, the point of the least digit goes
off.
Example: Setting set value to 500 °C.
5-2. AT (Auto tuning)
(1) Execution of AT action 
• By pressing the        or        key on AT action control
screen,            display on lower row turns into        and the
point of the least digit starts flashing, then the LED for AT
monitoring turns on to indicate AT standby.  Press
key to start AT action with point going off and LED for
AT monitoring flashing.
• When AT is carried out, ON/OFF action of output is
repeated several times, with the set value as the border
line, to make PID values stored in the memory and
terminates.  At the same time, control is started by using
stored PID constants.
The AT monitor LED goes out and the display on the AT
action control screen changes to            
ENT
key
ENT
key
key
0-0 basic screen
continuing
point flashing
point flashing
one by one
point goes off to 
indicate registration
key
key
ENT
key
0-0 basic screen
point goes off to 
indicate registration
0-1 
AT action control screen 
• LED for AT 
monitoring 
turns on
• LED for AT 
monitoring starts 
flashing 
AT 
action
Starting
point flashing
MAN
ENT