Avaya S8100 User Manual

Page of 408
1
Install and cable a G600 cabinet
Install equipment-room hardware for G600
S8100 Installation and Upgrades
95
November 2003
Each column of sneak fuse panels requires approximately 8 inches (20 cm) of horizontal wall space. 
Connector cables connect the network interface to the sneak fuse panel. Also, use 157B connecting 
blocks equipped with SCP-110 protectors for sneak-current protection.
NOTE:
Sneak-current protectors with a rating of 350 mA at 600 V must be UL-listed for United 
States installations or CSA-certified for Canadian installations. The panel contains 2 25-
pair connectors, fuse removal tool, and fifty 220029 sneak fuses (and 2 spares). Use the 
SCP-110 protectors with 110-type hardware and on the 507B sneak fuse panel. The SCP-
110 protectors can be ordered separately and installed on the 157B connecting block. Fifty 
protectors are required per block.
1
Install the 507B near the network interface or patch panels with locally-obtained #12 × ¾-inch 
screws (or equivalent).
 on page 95 is a pinout of the cable wiring and associated fuse 
numbers.
Table 8: Sneak fuse connector pinout  1 of 2
Connector Pin 
Numbers
Pair/Fuse 
Number
26/1
1
27/2
2
28/3
3
29/4
4
30/5
5
31/6
6
32/7
7
33/8
8
34/9
9
35/10
10
36/11
11
37/12
12
38/13
13
39/14
14
40/15
15
41/16
16
42/17
17
  1 of 2