Siemens A1 User Manual

Page of 74
International English 
Selecting a Drive 
MICROMASTER  Applications Handbook 
Selecting a Drive 
Often drive selection is straight forward, as a motor is already installed and the 
speed range requirement is not excessive.  However, when a drive system is 
selected from first principles, careful consideration may avoid problems in 
installation and operation, and may also save significant cost. 
3.1 Overall 
Considerations 
Check the Current rating of the inverter and the motor.  Power rating is only a 
rough guide. 
Check that you have selected the correct operating voltage.  230 V three-phase 
input MICROMASTERs will operate with single or three-phase inputs.  400 V 
MICROMASTERs are for three-phase application only.  Single-phase input units 
can be more cost effective in some cases, but note that 230 V units will be 
damaged if operated at 400 V.  See section 3.2.1. 
Check the speed range you require.  Operation above normal supply frequency (50 
or 60 Hz) is usually only possible at reduced power.  Operation at low frequency 
and high torque can cause the motor to overheat due to lack of cooling. 
Synchronous motors require de-rating, typically by 2-3 times.  This is because the 
power factor, and hence the current, can be very high at low frequency. 
Check overload performance.  The inverter will limit current to 150 or 200% of full 
current very quickly.  A standard, fixed speed motor will tolerate these overloads. 
Do you need to stop quickly?  If so, consider using a braking resistor to absorb the 
energy.  A separate braking unit may be required for some VSDs.  See section 0, 
Do you need to operate with cables longer than 50m, or screened or armored 
cables longer than 25m? If so, it may be necessary to de-rate, or fit a choke to 
compensate for the cable capacitance.  
3.2 
Supply Side Requirements 
In order to achieve reliable operation, the main power supply to the inverter system 
must be suited to the inverter and the anticipated power supplied. The following 
points should be considered: 
3.2.1 Supply 
Tolerance 
Inverters are usually designed to operate on a wide range of supply voltages.  For 
example: 
Low Voltage units    
 
200 - 240 V  ±10% i.e.  180 - 264 V 
High Voltage units   
 
380 - 480 V  ±10% i.e.  342 - 528 V 
Very High Voltage units   500 - 600 V  ±10% i.e.  450 - 660 V 
Inverters will operate over a wide supply frequency range, typically 47 - 63 Hz 
However, many supplies vary outside these voltage levels.  For example: