Simple Applications 
MICROMASTER  Applications Handbook 
23 
 
Advanced Features: 
025 
Enable DC brake.  The DC brake feature can be enabled to provide a 
holding torque if required.  See section 8.2. 
013/014 
Increase/decrease frequency (Motor Potentiometer function). 
099 
BiCo Functionality.  Many complex functions are possible.  
 
Please consult the Parameter List for additional details. 
 
Time
Possible control cycle using fixed frequencies, DC Braking, and 
Variable Ramp Rates
Output 
Frequency
Fixed Frequencies
Alternate Ramp time 
selected via digital input
DC Braking 
selected via digital input
 
Figure 5-3 
Composite Control Cycle 
5.5 
Using the control outputs 
There are several control outputs, which can be used to control external indicators 
or warn of potential problems. 
5.5.1 
Analog Output (MICROMASTER MM440 only). 
The analog output may be set to give several different indications as described in 
parameter P0771.  The output is 0-20 mA, but can be easily converted to a voltage 
by fitting a resistor (500 ohms for 0-10 V for instance), and to 4-20 mA using the 
scaling parameters such as P0778. 
5.5.2 Relays 
An indicator relay is provided which may be programmed to give a variety of 
indications using parameter P0731.  The relay is often used to indicate set point 
reached (P731=52.8), warning active (P731=52.7), output current exceeding a set 
value (P731=53.3). 
The relays can be used to control an external brake.  A timer function can be used 
to start the inverter and release the brake as described in parameter P1216.  In this 
case, the relay must be suppressed and a contactor used to switch the brake itself.  
See section 5.8.6. 
The relay contacts should be suppressed where inductive loads such as contactor 
coils or electromagnetic brakes are switched.